Product specifications

Characteristic
Value
Air ventYes
Application typeDirect Heating with mixing & Instantaneous DHW
CE evaluatedYes
Check valveYes
Circulation pumpYes
Connection directionBottom
Cover materialEPP
DCW static pressure [bar] [Min]2 bar
Depth with cover [mm]150 mm
DescriptionEvoFlat 4.0 M4, composite, floor heating, DHW HEX copper type 4
DG Indicator ProfileContains Gas
DH connection size3/4"
DH connection typeG int. Thread
DH pipe sizeØ18
DHW capacity [kW] [Max]80 kW
DHW capacity [kW] [Min]60 kW
DHW circulationOptional
DHW controller nameTPC-M
Differential pressure controllerIntegrated
Electrical connection230V 50 Hz
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Heating capacity [kW] [Max]18 kW
Characteristic
Value
Heating capacity [kW] [Min]10 kW
Heating circuit - controlThermostat
Heating control typeThermostatic + Differential pressure
Heating controller nameTPC-M
Heating system typeFloor heating
HEX heating brazing materialCopper
High temperature connection (HTC)Optional
In scope of WEEENo
Material DescriptionEvoFlat 4.0 M4
MeteringPrepared for water and energy meter
PipingPPS composite
Pressure nominal primary [bar]10 bar
Pressure nominal secondary [bar]10 bar
Product groupSmall Stations
Product lineSubsystems
Product TypeEvoFlat 4.0M
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Station size typeType 4
StrainerPrimary
Summer bypassYes
Supply temperature construction [˚C]95 °C
Thermal conductivity [W/mK]0.039 W/m-K

General specifications

Characteristic
Value
Gross weight14.6 Kilogram
Net weight13.4 Kilogram
Volume79.909 Liter
Characteristic
Value
EAN5702424547028
Proposition 65Cancer and Reproductive Harm