Danfoss logo
DSA WALL SWEDEN

Substations, DSA2 WALL, HE150 DHW80, 150 kW, Heating controller name: ECL 310, DHW controller name: ECL 310, DHW circulation: Yes

144B5037

DSA 2 WALL SE HE150 DHW80

Product specifications

Characteristic
Value
Allowed temperature [˚C] [Min]2 °C
Application typeIndirect Heating & Instantaneous DHW
ApprovalCE
Capacity [kW]150.0 kW
Category nameIndirect heating substations
CE markYes
China RoHS complianceOut of scope
Circulation connection sizeDN20
Circulation connection typeInternal thread
Circulation pipe sizeDN20
Connection direction primaryPrimary - Right or left, Secondary - Top & Top
Connection direction secondaryLeft / Right
Cover materialWhite-lacquered steel sheet
Cover optionNo
Delta P primary without heat meter [bar] [Min]1.44 bar
Depth with cover [mm]650 mm
Depth without cover [mm]650 mm
DescriptionDSA 2 WALL SE HE150 DHW80
DesignWall mounted
DG Indicator ProfileNot relevant for dangerous goods
DH connection sizeDN32
DH connection typeExternal thread
DH pipe sizeDN32
DHW circulationYes
DHW circulation pump brandGrundfos
DHW circulation pump typeUPS 25-60 N 180
DHW connection sizeDN25
DHW connection typeInternal thread
DHW Control typeElectronic
DHW controller nameECL 310
DHW HEX typeXB37M-20
DHW pipe sizeDN32
Differential pressure primary [bar] [Max]12 bar
Flow primary [m3/h] [Max]1.44 m³/h
HE connection sizeDN32
Characteristic
Value
HE connection typeInternal thread
HE pipe sizeDN25
Heating control typeElectronic
Heating controller nameECL 310
Heating HEX typeXB37L-10
Heating pump brandGrundfos
Heating pump typeMagna 3 25-100
Height with cover [mm]1200 mm
Height without cover [mm]1200 mm
HEX DHW alloy1.4404
HEX DHW brazed/gasketed materialBrazed copper
HEX heating alloy1.4404
HEX heating brazed/gasketed materialBrazed copper
Insulation materialEPP
Manufacturer's nameDanfoss
Material DescriptionDSA 2 WALL SE HE150 DHW80
Number of households [Max]10
Number of households [Min]5
Package depth [mm]800 mm
Package height [mm]800 mm
Package width [mm]1200 mm
PED category§ 3.3
Pressure nominal primary [bar]16 bar
Pressure nominal secondary [bar]10 bar
Pressure primary [bar] [Max]16 bar
Pressure secondary [bar] [Max]10 bar
Product groupSubstations
Product lineHeavy Duty Stations
Product TypeDSA2 WALL
Substation versionHE150 DHW80
Supply temperature construction [˚C]115 °C
Supply voltage [V] AC230 V
UL markNo
Width with cover [mm]650 mm
Width without cover [mm]800 mm

General specifications

Characteristic
Value
Gross weight15 Kilogram
Characteristic
Value
Net weight15 Kilogram