Product specifications

Characteristic
Value
Allowed temperature [˚C] [Min]2 °C
Application typeDHW storage & charging
ApprovalDVGWCE
Capacity [kW]40.0 kW
Category nameTank solution substations
CE evaluatedYes
China RoHS complianceOut of scope
Circulation connection sizeRp3/4"
Circulation connection typeinternal thread
Circulation pipe sizeDN20
Connection direction primary and secondaryhorizontal
Current [A] [Max]0.1 A
DCW static pressure [bar] [Min]1 bar
Delta P primary without heat meter [bar] [Min]0.11 bar
Depth with cover [mm]915 mm
DescriptionTHERMODUAL-S 300-40
Designstanding
DG Indicator ProfileNot relevant for dangerous goods
DH connection size26,9 mm
DH connection typewelded
DH pipe sizeDN20
DHW connection sizeRp1 1/2"
DHW connection typeinternal thread
DHW pipe sizeDN40
DHW pump brandGrundfos
DHW pump typeUPM2K
Differential pressure primary [bar] [Max]25 bar
EU RoHS complianceOut of scope
Flow primary [m3/h] [Max]0.76 m³/h
Flow secondary [m3/h] [Max]0.69 m³/h
HE connection size26,9 mm
HE connection typewelded
Characteristic
Value
HE pipe sizeDN20
Height with cover [mm]1760 mm
HEX DHW alloy1.4404
HEX DHW brazing materialCopper
HEX DHW typeBrazed
Hot water tank volume [l]300 L
In scope of WEEE and contain batteriesNo
Insulation materialEPS with laminated fleece
Manufacturer's nameDanfoss
Material DescriptionThermoDual-S 300-40 v2023
Number of households [Max]17
Package 2 depth [mm]800 mm
Package 2 height [mm]500 mm
Package 2 width [mm]1200 mm
Package depth [mm]750 mm
Package height [mm]1910 mm
Package width [mm]750 mm
PED category§ 4.3
Pressure nominal primary [bar]25 bar
Pressure nominal secondary [bar]10 bar
Pressure primary [bar] [Max]25 bar
Pressure secondary [bar] [Max]10 bar
Product groupDHW system
Product lineHeavy Duty Stations
Product TypeTD-S
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Supply temperature construction [˚C]150 °C
Supply temperature recommended [˚C]70 °C
Supply voltage [V] AC230 V
Tank material14571
UK RoHS complianceOut of scope
Width with cover [mm]890 mm

General specifications

Characteristic
Value
Gross weight73 Kilogram
Net weight73 Kilogram
Characteristic
Value
EAN5715162705551
Proposition 65Cancer and Reproductive Harm