Danfoss logo
RT temperature Switch with room sensor

Thermostat, RT16L

017L002466

Temperature range [°C]: 0 - 38, Reset function: Auto, Contact function: SPDT (neutral zone), Sensor type: Room sensor, Enclosure rating IP: IP66

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-50 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-58 °F
ApprovalCCCCEEACLLC CDC EURO-TYSKLVDPZHRMRSRoHSRoHS ChinaTYSK
CE evaluatedYes
Charge typeState Vapour
China RoHS complianceYes
Contact differential [°C] [max]1.5 °C
Contact differential [°C] [min]0.7 °C
Contact functionSPDT (neutral zone)
Contact ratingAC15=3 A, 400 VAC1=10 A, 400 VAC3=4 A, 400 VDC13=12 W, 220 VLR=28 A, 400 V
DG Indicator ProfileOther Dangerous Goods
Diff. @ Max. range setting[°C] [max]1.9 °C
Diff. @ Max. range setting[°C] [min]0.7 °C
Diff. @ Min. range setting[°C] [max]5.0 °C
Diff. @ Min. range setting[°C] [min]1.5 °C
Differential typeAdjustable
EL Number FI3530115
Electrical conn. Male/FemaleFemale
Electrical connectionScrewed cable entry
Electrical connection size2xPg 13.5
Electrical connection standardDIN 40430
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400VPollution degree: 3Rated impulse voltage: 4 kVShort circuit prot, fuse: 10A
EN 60947 wiring propertiesFlex, ferrules: 0.2-1.5 mm2Flex, no ferrules: 0.2-2.5 mm2Solid/stranded: 0.2-2.5 mm2
Enclosure rating IPIP66
Characteristic
Value
EU RoHS complianceYes
EU RoHS exemption clauseNo
In scope of WEEE and contain batteriesNo
Material DescriptionRT16L Thermostat M/15
Max. neutral zone [°C]5.0 °C
Max. sensor temperature [°C]100 °C
Max. sensor temperature [°F]212.0 °F
Packing formatMulti pack
Product accessoriesSwitches accessories
Product descriptionThermostat
Product groupSwitches and thermostats
Product lineAir Conditioning and Commercial Refrigeration
Product nameThermostat
Product TypeRT16L
Quantity per packing format15 pc
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
SCIP dossier no.c4c20ce6-4a07-4caa-9394-1e7d8b13ffec
Sensor typeRoom sensor
ServiceableContact systems
Temperature range [°C] [max]38 °C
Temperature range [°C] [min]0 °C
Temperature range [°F] [max]100 °F
Temperature range [°F] [min]32 °F
UK RoHS complianceYes
VVS Number DK472242100
VVS Number NO9007552

General specifications

Characteristic
Value
Gross weight0.933 Kilogram
Net weight0.821 Kilogram
Volume2.685 Liter
Characteristic
Value
EAN5702428042642
Proposition 65Cancer and Reproductive Harm