Danfoss logo
Termix BVX-FI RO T/E 2-2 144H2377 - 2-3 STW 144H2378

Termix BVX FI RO, Type 2-2, Heating controller name: ECL310, DHW controller name: RAVK

144H2377

Product Type: Termix BVX FI RO, Type 2-2, 16 bar, 120 °C, ECL310, RAVK

Product specifications

Characteristic
Value
Application typeIndirect Heating & Primary connected DHW cylinder
CE evaluatedYes
China RoHS complianceOut of scope
Circulation connection size3/4"
Circulation connection typeinternal thread
Circulation pipe sizeØ18
Cover materialWhite-lacquered steel sheet
Cover optionIncluded
Depth with cover [mm]570 mm
DescriptionSubstation - Indirect Heating + DHW cylinder
DG Indicator ProfileContains Gas
DH connection size3/4"
DH connection typeinternal thread
DH pipe sizeØ18
DHW circulationOptional
DHW connection size3/4"
DHW connection typeinternal thread
DHW Control typeThermostatic
DHW controller nameRAVK
DHW pipe sizeØ18
DHW tank circuit - controlThermostatic
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
HE connection size3/4"
Characteristic
Value
HE connection typeinternal thread
HE pipe sizeØ18
Heating circuit - controlECL310
Heating control typeElectronic
Heating controller nameECL310
Height with cover [mm]1910 mm
HEX heating brazing materialCopper
HEX heating typeBrazed
Hot water tank volume [l]105 L
In scope of WEEE and contain batteriesNo
Material DescriptionTermix BVX-FI RO T/E 2-2
Pressure nominal primary [bar]16 bar
Product groupSmall Stations
Product lineLight Duty Stations
Product TypeTermix BVX FI RO
REACH Candidate List substancesLead (CAS no. 7439-92-1)
SCIP dossier no.d457aeb9-ee89-4efe-84f2-52db46c8e7f5
Station size typeType 2-2
Supply temperature construction [˚C]120 °C
Supply voltage [V]230.0 V
Tank materialEnamelled steel
UK RoHS complianceOut of scope
UL evaluatedOut of scope
Width with cover [mm]560 mm

General specifications

Characteristic
Value
Gross weight125 Kilogram
Net weight125 Kilogram
Volume0.684 Cubic meter
Characteristic
Value
EAN5706561321718
Proposition 65Cancer and Reproductive Harm