Danfoss logo
VXe Solo H, 145F4509

VXe Solo H, Type 2, Heating controller name: ECL 310 / P330

145F4509

Product Type: VXe Solo H, Type 2, 16 bar, 120 °C, ECL 310/AVQM/AMV 150

Product specifications

Characteristic
Value
Application typeIndirect Heating
Capacity [kW]30.0 kW
China RoHS complianceOut of scope
Connection directionBottom
Contain batteriesNo
Cover materialPolypropylene
DG Indicator ProfileNot relevant for dangerous goods
DH connection size3/4"
DH connection typeExternal thread
DH pipe sizeØ18
Depth with cover [mm]315 mm
Depth without cover [mm]315 mm
DescriptionVXe Solo H, Type 2, ECL310/P330, with HM
Differential pressure controllerIntegrated in control valve
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
HE connection size3/4"
HE connection typeInternal thread
HE pipe sizeØ18
HEX heating brazed/gasketed materialBrazed copper
Heating ActuatorAMV 150
Heating Control valveAVQM 15
Heating HEX typeXB06H-1 40
Characteristic
Value
Heating control typeElectronic
Heating controller nameECL 310 / P330
Heating pump brandGrundfos
Heating pump typeUPM3 Auto 15-70 130
Height with cover [mm]785 mm
Height without cover [mm]785 mm
In scope of WEEENo
Insulation materialPolypropylene
Material DescriptionVXe Solo H,typ2,ECL310/P330 W HM,W/O MAG
Material Description (Short TeVXe Solo H, Type 2, ECL 310/P330, HM
Mixing circuit - controlECL 310/AVQM/AMV 150
Pressure nominal primary [bar]16 bar
Product TypeVXe Solo H
Product groupSmall Stations
Product lineLight Duty Stations
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Station size typeType 2
Supply temperature construction [˚C]120 °C
Supply voltage [V] AC230 V
UL evaluatedOut of scope
Width with cover [mm]550 mm
Width without cover [mm]550 mm

General specifications

Characteristic
Value
Gross weight38 Kilogram
Net weight36 Kilogram
Volume173.91 Liter
Characteristic
Value
EAN/UPC5715162877029
Proposition 65Cancer and Reproductive Harm