Danfoss logo
DSP MOD@ single station for France

Substations, DSP MOD, Heating controller name: ECL310

200B0013

DSP1-MOD@-IB032-040-0000-ML-FR-PN25-0128, 128 kW, ECL310, Lacroix Sofrel, Distech, 25 bar, 110°C

Product specifications

Characteristic
Value
Allowed temperature [˚C] [Min]2 °C
Application typeIndirect Heating
ApprovalCE
Approval standardCE
Category nameIndirect heating substations
CE evaluatedYes
Cover materialWithout
Cover optionNo
Depth without cover [mm]790 mm
DescriptionDSP1-MOD@-IB032-040-0000-ML-FR-PN25-0128, 128 kW, ECL310, Lacroix Sofrel, Distech, 25 bar, 110°C
Designstanding
DG Indicator ProfileNot relevant for dangerous goods
DH connection size1 1/4"
DH connection typeThread
DH pipe sizeDN32
Differential pressure primary [bar] [Max]16 bar
Fitting pieceheatmeter
Flow primary [m3/h] [Max]3.72 m³/h
Flow secondary [m3/h] [Max]5.58 m³/h
HE connection sizeRp1 1/2"
HE connection typeThread
Characteristic
Value
HE pipe sizeDN40
Heating control typeElectronic
Heating controller nameECL310
Height without cover [mm]1640 mm
HEX heating alloy1.4404
HEX heating brazing materialCopper
HEX heating typeBrazed
Insulation materialPU Hard Foam
Manufacturer's nameDanfoss
Material DescriptionDSP1-MOD@-IB032-040-0000-ML-FR-PN25-0128
Pressure nominal primary [bar]25 bar
Pressure nominal secondary [bar]16 bar
Pressure primary [bar] [Max]25 bar
Pressure secondary [bar] [Max]16 bar
Product groupSubstations
Product lineHeavy Duty Stations
Product TypeDSP MOD
Sensor type heatmeterpocket 6mm
Supply temperature construction [˚C]110 °C
Supply voltage [V] AC230 V
Width without cover [mm]2020 mm