Danfoss logo
DSA HRU, Two-tanks solution, Direct heating substations,

DSA HRU, Two-tanks solution, Heating demand capacity [kW]: 540, Heat recover (CO2) capacity [kW]: 100, Heat resale option: NO

146B9262

DSA HRU 2 HE 540D CO2 100

Product specifications

Characteristic
Value
Additional informationTwo-tanks solution
Allowed temperature [˚C] [Min]2 °C
ApplicationA4
Application typeHeat recovery unit
ApprovalCE
CE evaluatedYes
Connection direction primary and secondaryUp
Contain batteriesNo
Cover optionNo
DG Indicator ProfileNot relevant for dangerous goods
DH connection sizeDN65
DH connection typeflange
DH pipe sizeDN65
Data communicationModBus
Depth without cover [mm]1200 mm
DescriptionDSA HRU 2 HE 540D CO2 100
Flow primary [m3/h] [Max]1.55 m³/h
HE connection sizeDN65
HE connection typeflange
HE pipe sizeDN65
HEX heating alloy1.4404
HEX heating brazed/gasketed materialBrazed copper
Heat recover (CO2) capacity [kW]100 kW
Characteristic
Value
Heat resale optionNO
Heating HEX typeXB59M-1 90
Heating control typeElectronic
Heating controller nameECL310 (P510.12)
Heating demand capacity [kW]540 kW
Height without cover [mm]2000 mm
Insulation materialPU Hard Foam
Manufacturer's nameDanfoss
Material DescriptionDSA HRU 2 HE 540D CO2 100
Operating temperature [°C] [max]90 °C
PED categoryI
Pressure nominal primary [bar]10 bar
Pressure nominal secondary [bar]10 bar
Product TypeDSA HRU
Product groupSubstations
Product lineHeavy Duty Stations
Storage tank quantity2 pc
Storage tank volume500.0 L
Substation versionA4
Supply voltage [V] AC [max]230 V
UL evaluatedOut of scope
Width without cover [mm]2800 mm

General specifications

Characteristic
Value
Gross weight540 Kilogram
Net weight500 Kilogram
Characteristic
Value
EAN/UPC5715162903940