Danfoss logo
DSA HRU, Two-tanks solution, Direct heating substations

DSA HRU, Two-tanks solution, Heating demand capacity [kW]: 216, Heat recover (CO2) capacity [kW]: 150, Heat resale option: YES

146B9222

DSA HRU 2 HE 216D CO2 150 S

Product specifications

Characteristic
Value
Additional informationTwo-tanks solution
Allowed temperature [˚C] [Min]2 °C
ApplicationA3
Application typeHeat recovery unit
ApprovalCE
CE evaluatedYes
Charging pump brandWilo
Charging pump typeSTRATOS-PARA 25/1-12
Connection direction primary and secondaryUp
Cover optionNo
Data communicationModBus
Depth without cover [mm]1200 mm
DescriptionDSA HRU 2 HE 216D CO2 150 S
DG Indicator ProfileNot relevant for dangerous goods
DH connection size2"
DH connection typeThread
DH pipe sizeDN50
Flow primary [m3/h] [Max]3.87 m³/h
HE connection size2"
HE connection typeThread
HE pipe sizeDN50
Heat recover (CO2) capacity [kW]150 kW
Heat resale optionYES
Heating control typeElectronic
Heating controller nameECL310 (P510.12)
Heating demand capacity [kW]216 kW
Characteristic
Value
Heating HEX typeXB37H-1 60
Height without cover [mm]2000 mm
HEX heating alloy1.4404
HEX heating brazing materialCopper
HEX heating typeBrazed
HEX type for selling optionXB37H-1-60
In scope of WEEE and contain batteriesNo
Insulation materialPU Hard Foam
Manufacturer's nameDanfoss
Material DescriptionDSA HRU 2 HE 216D CO2 150 S
Operating temperature [°C] [max]90 °C
PED categoryI
Pressure nominal primary [bar]10 bar
Pressure nominal secondary [bar]10 bar
Product groupSubstations
Product lineHeavy Duty Stations
Product TypeDSA HRU
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Resale pump brandSTRATOS-PARA 25/1-12
Resale pump typeWilo
Storage tank quantity2 pc
Storage tank volume500.0 L
Substation versionA3
Supply voltage [V] AC [max]230 V
Width without cover [mm]2800 mm

General specifications

Characteristic
Value
Gross weight540 Kilogram
Net weight500 Kilogram
Characteristic
Value
EAN5715162902721
Proposition 65Cancer and Reproductive Harm