Danfoss logo
DSA HRU, Two-tanks solution, Indirect heating substations

DSA HRU, Two-tanks solution, Heating demand capacity [kW]: 338, Heat recover (CO2) capacity [kW]: 150, Heat resale option: NO

146B9174

DSA HRU 2 HE 338 CO2 150

Product specifications

Characteristic
Value
Additional informationTwo-tanks solution
Allowed temperature [˚C] [Min]2 °C
ApplicationA2
Application typeHeat recovery unit
ApprovalCE
CE evaluatedYes
Connection direction primary and secondaryUp
Contain batteriesNo
Cover optionNo
DG Indicator ProfileNot relevant for dangerous goods
DH connection size2"
DH connection typeThread
DH pipe sizeDN50
Data communicationModBus
Depth without cover [mm]1200 mm
DescriptionDSA HRU 2 HE 338 CO2 150
Flow primary [m3/h] [Max]9.68 m³/h
HE connection size2"
HE connection typeThread
HE pipe sizeDN50
HEX heating alloy1.4404
HEX heating brazed/gasketed materialBrazed copper
Heat recover (CO2) capacity [kW]150 kW
Characteristic
Value
Heat resale optionNO
Heating HEX typeXB59M-1 90
Heating control typeElectronic
Heating controller nameECL310 (P510.12)
Heating demand capacity [kW]338 kW
Height without cover [mm]2000 mm
Insulation materialPU Hard Foam
Manufacturer's nameDanfoss
Material DescriptionDSA HRU 2 HE 338 CO2 150
Operating temperature [°C] [max]90 °C
PED categoryI
Pressure nominal primary [bar]10 bar
Pressure nominal secondary [bar]6 bar
Product TypeDSA HRU
Product groupSubstations
Product lineHeavy Duty Stations
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Storage tank quantity2 pc
Storage tank volume500.0 L
Substation versionA2
Supply voltage [V] AC [max]230 V
UL evaluatedOut of scope
Width without cover [mm]2800 mm

General specifications

Characteristic
Value
Gross weight540 Kilogram
Net weight500 Kilogram
Characteristic
Value
EAN/UPC5715162903124
Proposition 65Cancer and Reproductive Harm