Danfoss logo
 S 22

S 22 (A266), M50, Heating controller name: ECL 310 / A266, DHW controller name: ECL 310 / A266

145G4415

Product Type: S 22 (A266), M50, 10 bar, 110 °C, ECL 310 / A266

Product specifications

Characteristic
Value
Application typeDirect Heating with mixing & Instantaneous DHW
China RoHS complianceOut of scope
Connection directionBottom
Contains batteriesNo
Cover materialWhite-lacquered steel sheet
DG Indicator ProfileNot relevant for dangerous goods
DH connection size1"
DH connection typeInternal thread
DH pipe sizeØ22
DHW ActuatorAMV 30
DHW Control typeElectronic
DHW Control valveVM2 20
DHW HEX typeXB37M-1 50
DHW circulationYes
DHW connection size1"
DHW connection typeInternal thread
DHW control valve kvs value [m3/h]4.00
DHW controller nameECL 310 / A266
DHW pipe sizeØ22
Depth with cover [mm]400 mm
Depth without cover [mm]370 mm
DescriptionS22 (35) XB37M50, ECL310/A266 ISO mK Std
Differential pressure controllerAVP-F
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
HE connection size1"
Characteristic
Value
HE connection typeInternal thread
HE pipe sizeØ22
HEX DHW brazed/gasketed materialBrazed copper
Heating ActuatorAMV 10
Heating Control valveVM2 15
Heating control typeElectronic
Heating controller nameECL 310 / A266
Heating pump brandWilo
Heating pump typePara 15-130/6-43/SC-12
Height with cover [mm]1037 mm
Height without cover [mm]1037 mm
In scope of WEEENo
Material DescriptionS22 (35) XB37M50, ECL310/A266 ISO mK Std
Material Description (Short TeS 22, M50, ECL 310/A266, Std. (35)
Pressure nominal primary [bar]10 bar
Product TypeS 22 (A266)
Product groupSmall Stations
Product lineLight Duty Stations
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Station size typeM50
Supply temperature construction [˚C]110 °C
Supply voltage [V] AC230 V
UL evaluatedOut of scope
Width with cover [mm]600 mm
Width without cover [mm]545 mm

General specifications

Characteristic
Value
Gross weight52 Kilogram
Net weight50 Kilogram
Characteristic
Value
EAN/UPC5715162519653
Proposition 65Cancer and Reproductive Harm