AVTB (fast), PN 16, DN 15, 1.90 m³/h, 20 °C - 60 °C, 2.0 m, Internal thread
003N8229
AVTB PN16 15/1,9 20-60 2m int Rp return
Product specifications
Characteristic | Value |
---|---|
Ambient temperature [°C] [max] | 70 °C |
Ambient temperature [°C] [min] | 0 °C |
Approval standard | ETA VA 1.54/18952 |
Basic Data Text Template | Thermostatisches Wasserventil AVTB<br>Regler ohne Fremdenergie zur Temperatur-<br>regelung von Flüssigkeiten, bei steigen-<br>der Temperatur schließend, Ventilkegel<br>druckentlastet, Ventilgehäuse MS 58,<br>Anschluss Rohrgewinde,<br>Kapillarrohrlänge 2 m,<br>Montage des Reglers im Rücklauf<br>Fühler ist an der Stelle zu montieren,<br>an welcher die Anlagentemperatur<br>wärmer ist als die Temperatur am Regler<br>Fühler aus Kupfer R 3/4<br>Einbaulage des Fühlers beachten!<br>max. Medientemperatur 130 C, PN 16,<br>max Differenzdruck 10 bar,<br>Sollwertbereich: 20-60 Grad C<br>max. Fühlertemperatur: 90 Grad C<br>Abmessungen Fühler: 9,5 x 180<br>Anschluss: DN 15, IG Rp 1/2<br>kvs-Wert: 1.9<br>Fabrikat: Danfoss<br>Typ: AVTB 15<br>Bestell-Nr.: 003N8229 |
Capillary tube length [m] | 2.0 m |
Cavitation factor | 0.40 |
Cone /seat sealing material | NBR / Brass W. No 2.0402 |
Connection size | Rp 1/2 |
Connection standard | ISO 7/1 |
Connection types | Internal thread |
Contain batteries | No |
DG Indicator Profile | Contains Gas |
Description | AVTB PN16 15/1,9 20-60 2m int Rp return |
Diameter [mm] | 15 mm |
Differential pressure range [bar] [Max] | 10.00 bar |
EU RoHS compliance | Yes with exemptions |
EU RoHS exemption clause | 6(c) |
Flow characteristic | Linear |
Flow control | No |
Function | Temp. controller |
Function VSP - P | No |
Function VSP - Q | No |
Function VSP - T | Yes |
Impulse tube material | Copper mat. No 2.0090 |
Kvs values [m³/h] | 1.90 m³/h |
Material Description | AVTB PN16 15/1,9 20-60 2m int Rp return |
Media pH [Max] | 10 |
Media pH [Min] | 7 |
Media temperature [°C] [Max] | 130 °C |
Media temperature [°C] [Min] | 2 °C |
Media temperature at sensor [°C] [Max] | 90 °C |
Characteristic | Value |
---|---|
Medium alternative | Glycolic water up to 30% |
Mounting version | Return |
Number of ports | 2 |
PN alternative VSP | 10 |
Permissible media | District heating/cooling circulation water |
Pressure class | PN 16 |
Pressure nominal [bar] | 16 bar |
Product Type | AVTB (fast) |
Product group | Temperature controllers |
Product line | District Energy Controls |
REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
Rection time close [sec] | 3 " |
Rection time open [sec] | 3 " |
Return limiter function | No |
SCIP dossier no. | 1d2d0fb5-296e-403f-8017-ab8b8655c2d8 |
SCIP dossier product name | AVTB PN16 15/1,9 20-60 2m int Rp return |
Sensor connection | M14x1 / R1/2 ext thread acc. DIN 2999 |
Temperature control | Yes |
Temperature sensor diameter [mm] | 9.5 mm |
Temperature sensor length [mm] | 180 mm |
Temperature sensor material | Copper mat. No 2.0090 |
Temperature sensor mounting | Sensor warmer |
Temperature setting range [°C] [Max] | 60 °C |
Temperature setting range [°C] [Min] | 20 °C |
Time constant [sec] | 3 " |
Transport temperature [°C] [Max] | 50 °C |
Transport temperature [°C] [Min] | -20 °C |
Valve body material | Brass CuZn40Pb2 W. no 2.0402 |
Valve cone material | NBR rubber |
Valve seat material | Cr Ni steel W.no 1.4301 |
Valve size | DN 15 |
General specifications
Characteristic | Value |
---|---|
Gross weight | 1.584 Kilogram |
Net weight | 1.482 Kilogram |
Characteristic | Value |
---|---|
EAN/UPC | 5702421100899 |
Proposition 65 | Cancer and Reproductive Harm |