Pressure switch, KPU5
060-5241
Regulation range [bar] Pe: 8.00 - 32.00, Differential [bar]: 1.80 - 6.00, Contact function: SPST(NO), Reset function: Auto, Pressure connection type: Flare, Pressure connection size: 1/4, Pressure Male/Female: Male, Enclosure rating IP: IP30, Max. Working Pressure [bar]: 35.0
Product specifications
Characteristic | Value |
---|---|
Amb. Temp. Note | 80 °C/176 °F for max 120 min |
Ambient temperature range [°C] [max] | 50 °C |
Ambient temperature range [°C] [min] | -40 °C |
Ambient temperature range [°F] [max] | 122 °F |
Ambient temperature range [°F] [min] | -40 °F |
Application note | Not applicable for liquid line |
Approval | CELVDRoHSc UL us UL873, CS C22.2 |
CE evaluated | Yes |
China RoHS compliance | Out of scope |
Contact function | SPST(NO) |
Contact rating | 144 A, 240 V AC24 A, 240 V acDC=12 W pilot dutyFLA=24 A, 120 V acLRA = 144 A, 120 V ac |
DG Indicator Profile | Not relevant for dangerous goods |
Differential [bar] [max] | 6.00 bar |
Differential [bar] [min] | 1.80 bar |
Differential [psi] [max] | 85.00 psi |
Differential [psi] [min] | 25.00 psi |
Electrical conn. comments | for ½ in male pipe thread |
Electrical connection | Hole |
Electrical connection size | 7/8 in |
EN 60947 electrical properties | Insulation: 400VPollution degree: 3Rated impulse voltage: 4 kVShort circuit prot, fuse: 16A |
EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2Flex, no ferrules: 0.7-2.5 mm2Solid/stranded: 0.75-2.5 mm2 |
Enclosure rating IP | IP30 |
Enclosure rating Nema (~) | 1 |
EU RoHS compliance | Yes |
EU RoHS exemption clause | No |
In scope of WEEE and contain batteries | No |
Lubricants compatibility | Oilfree applications |
Material Description | KPU5 Pressure Switch M/14 |
Max. test pressure [bar] Pe | 36.5 bar |
Characteristic | Value |
---|---|
Max. test pressure [psig] | 529.0 psig |
Max. Working Pressure [bar] | 35.0 bar |
Max. Working Pressure [psig] | 510 psig |
Oil free refrigerants | R134aR513AR515B |
Packing format | Multi pack |
Pressure connection size | 1/4 |
Pressure connection standard | DIN 8906 |
Pressure connection type | Flare |
Pressure Male/Female | Male |
Pressure sensing element | Bellows |
Product accessories | Switches accessories |
Product description | Fan Control |
Product group | Switches and thermostats |
Product line | Air Conditioning and Commercial Refrigeration |
Product name | Pressure switch |
Product Type | KPU5 |
Quantity per packing format | 14 pc |
REACH Candidate List substances | No |
Refrigerants | R113R124R134aR22R404AR407AR407CR407FR407HR422BR422DR438AR448AR449AR449BR450AR452AR507AR513AR515B |
Regulation range [bar] Pe [max] | 32.00 bar |
Regulation range [bar] Pe [min] | 8.00 bar |
Regulation range [psig] Pe [max] | 465.00 psig |
Regulation range [psig] Pe [min] | 100.00 psig |
Reset function | Auto |
Serviceable | No |
UK RoHS compliance | Out of scope |
UL approval file name | E31024 |
UL approved refrigerants | R113R124R134aR22R404AR407AR407CR407FR407HR422BR422DR438AR448AR449AR449BR450AR452AR507AR513AR515B |
UL evaluated | Yes |
General specifications
Characteristic | Value |
---|---|
Gross weight | 0.675 Kilogram |
Net weight | 0.64 Kilogram |
Volume | 0.832 Liter |
Characteristic | Value |
---|---|
EAN | 5702428063708 |
Proposition 65 | Cancer and Reproductive Harm |