Danfoss logo
MRS - L_ACB_Manual, Cable, Solder Odm,

Cartridge pressure switch, ACB, 31.00 bar, 24.00 bar

061F9613

Higher activ. pressure [bar]: 31.00, Lower activ. pressure [bar]: 24.00, Reset function: Manual, Contact function: SPST(NC), Pressure connection type: Solder, ODM, Electrical connection: Cable, Enclosure rating IP: IP65

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]85 °C
Ambient temperature range [°C] [min]-30 °C
Ambient temperature range [°F] [max]185 °F
Ambient temperature range [°F] [min]-20 °F
ApprovalC UL US UL873CE 0035TÜV
Burst pressure [bar]200.0 bar
Burst pressure [psig]2900 psig
Cable length [in]3.94 in
Cable length [m]0.100 m
Cable typeAWG18
CE evaluatedYes
China RoHS complianceYes exceed limitations
Contact functionSPST(NC)
Contact ratingAC=6 A, 250 V
DG Indicator ProfileNot relevant for dangerous goods
Electrical connectionCable
Enclosure rating IPIP65
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Higher activ. pressure [bar]31.00 bar
Higher activ. pressure [psi]450 psi
HousingEpoxy type
In scope of WEEE and contain batteriesNo
Lower activ. pressure [bar]24.00 bar
Lower activ. pressure [psi]348 psi
Lubricants compatibilityOilfree applications
Material DescriptionACB Cartridge Switch 2UB744MW I/100
Max. Working Pressure [bar]45.0 bar
Characteristic
Value
Max. Working Pressure [psig]653 psig
Medium temperature range [°C] [max]135 °C
Medium temperature range [°C] [min]-55 °C
Medium temperature range [°F] [max]275 °F
Medium temperature range [°F] [min]-70 °F
MountingVertical +/- 45º
Oil free refrigerantsR134aR513A
Packing formatIndustrial pack
Pressure connection notesCu-tube (tip=7mm)
Pressure connection size [mm]6.00 mm
Pressure connection typeSolder, ODM
Pressure range categoryHigh pressure
Product accessoriesSwitches accessories
Product groupSwitches and thermostats
Product lineAir Conditioning and Commercial Refrigeration
Product nameCartridge pressure switch
Product TypeACB
Quantity per packing format100 pc
REACH Candidate List substancesNo
RefrigerantsR125R134aR22R404AR407CR407HR410AR438AR448AR449AR452AR513A
Reset functionManual
ServiceableNo
Specification keyACB-2UB744MW
UK RoHS complianceYes with exemptions
UK RoHS exemption clause18
UL approved refrigerantsR125R134aR22R404AR407CR407HR410AR438AR448AR449AR452AR513A
UL evaluatedYes
Wire colourBlack

General specifications

Characteristic
Value
Gross weight0.044 Kilogram
Net weight0.042 Kilogram
Characteristic
Value
Volume0.123 Liter
EAN5702428258838