Danfoss logo
 single rotolock SY240 SZ240- 8556098

Scroll compressor, SY240A4PBE

SY240A4PBM

Refrigerants: R407C; R134a; R513A; R22, Segment usage: Air conditioning, Compressor power supply [V]: 380-415/3/50 460/3/60, Packing format: Industrial pack

Product specifications

Characteristic
Value
ApprovalCEULUKCA
Brand techniqueScroll compressor
Capacity controlFixed speed
CE evaluatedYes
China RoHS complianceYes exceed limitations
ColourBlue
Compressor power supply [V]380-415/3/50 460/3/60
Configuration codeSingle
Connection typeRotolock
DescriptionSY240-4
DG Indicator ProfileNot relevant for dangerous goods
Diameter [mm]344 mm
Discharge connection height [mm]654 mm
Discharge connection pipe size [in]1-1/8 in
Discharge connection size [in]1-3/4 in
DLLP4
Drawing number8556098b
EconomizerNo
EU RoHS complianceYes with exemptions
EU RoHS exemption clause7(c)-I6(a)6(a)-I6(c)7(a)8(b)
Factory HP [bar]33 bar
Factory LP [bar]25 bar
FamilySY
Fitting remark(shipped with rotolock version only)
Fitting sleeveODF
Fitting standardRotolock
Frequency [Hz]50/60
Gauge port HPNone
Gauge port LPSchrader
Glass mountingThreaded
Glass torque [Nm]50 N-m
GP LP torque [Nm]15 N-m
High Side TS Max150.0 °C
High Side TS Min-35.0 °C
High Side Volume5.0 L
High value of nominal voltage at 50Hz [V]400 V
High value of nominal voltage at 60Hz [V]460 V
High value of voltage range at 50Hz [V]440 V
High value of voltage range at 60Hz [V]506 V
In scope of WEEE and contain batteriesNo
IP protection classIP54 (with cable gland)
Low Side TS Max52.0 °C
Low Side TS Min-35.0 °C
Low Side Volume34.1 L
Low value of nominal voltage at 50Hz [V]380 V
Low value of nominal voltage at 60Hz [V]460 V
Low value of voltage range at 50Hz [V]342 V
Low value of voltage range at 60Hz [V]414 V
LRA215 A
Material DescriptionSY240-4PB-INDUST
Max pressure (PS) - high side31.80 bar
Max pressure (PS) - low side20.00 bar
MCC50 A
Model numberSY240A4PBE
Motor protectionElectronic protection module, 110/240 V
Characteristic
Value
Mounting torque [Nm]40.00 N-m
Network power supply [V/Ph/Hz]380-415/3/50 460/3/60
Number of starts per hour [Max]12
Oil charge [L]8.00 L
Oil drain1/4'' flare
Oil drain torque [Nm]35 N-m
Oil equalization1/2'' flare
Oil equalization torque [Nm]66 N-m
Oil reference320SZ
Packaging height [mm]904 mm
Packaging length [mm]1140 mm
Packaging weight [Kg]635 kg
Packaging width [mm]950 mm
Packing formatIndustrial pack
Packing quantity4
Phase3
Power connectionsStud M5
Product groupHermetic compressors
Product lineCommercial Compressors
Product nameScroll compressor SY
Product TypeSY240
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Refrigerant charge [kg] [Max]16.00 kg
RefrigerantsR134aR22R407CR513A
Reverse rotation protectionElectronic module
RLA35.7 A
Rotational speed at 50Hz [rpm]2900 rpm
Rotational speed at 60Hz [rpm]3500 rpm
SCIP dossier no.a92ec178-0979-4d30-af46-57b56ac94204
SCIP dossier product nameSY240-300/SZ240-300
Segment usageAir conditioning
Shipped fittingsSuction and discharge solder sleeves, rotolock nuts and gaskets
Shipped instructionsInstallation instructions
Shipped moduleElectronic protection module mounted in terminal box
Shipped mountingMounting kit with grommets and sleeves
Shipped oilInitial oil charge
Suction connection height [mm]196 mm
Suction connection material-
Suction connection pipe size [in]1-5/8 in
Suction connection size [in]2-1/4 in
Swept volume [cm3]347.80 cm³
TechnologyScroll
Test dif [bar] [Max]24 bar
Test HP [bar] [Max]32.0 bar
Test LP [bar] [Max]20.0 bar
Torque earth [Nm]4.00 N-m
Torque power [Nm]3.00 N-m
Total height [mm]727.0 mm
U.S. EPA labelFor installations using U.S. EPA restricted refrigerants, this product may be used for servicing existing equipment only.
UK RoHS complianceYes with exemptions
UK RoHS exemption clause192124121318
UL evaluatedYes
Viscosity [cP]68.0 cP
Winding resistance for three-phase compressors with identical windings [Ohm]0.616 Ohm

General specifications

Characteristic
Value
Gross weight157.5 Kilogram
Net weight152.27 Kilogram
Volume0.1 Cubic meter
Characteristic
Value
EAN5702428660709
Proposition 65Cancer and Reproductive Harm