Segment usage: Medium Back Pressure, Refrigerants: R404A; R507A; R452A; R407A; R134a; R407F; R513A; R448A; R449A, Compressor power supply [V]: 400/3/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]5200 m³/h
Air volume (EF002618)5200
ApplicationsMBP
China RoHS complianceOut of scope
Compression method (EF013498)Scroll compressor
Compressor modelMLZ038T4
Compressor power supply [V]400/3/50
Condenser Coil Internal Volume [L]1.62 L
Condenser typeG7
Connection typeSolder
Connection voltage (EF003625)230
Contains batteriesNo
CoolselectorFilterActive models
Depth (EF000049)1190
DescriptionOP-MSXM080MLW05E
DG Indicator ProfileNot relevant for dangerous goods
Electrical codeE
EU RoHS complianceOut of scope
FamilyOptyma™ Slim Pack
Fan blade size [mm]500.000 mm
Fan cowl/grill typeB3
Fan current @ 50Hz [A]0.96 A
Fan diameter [mm]500 mm
Fan power consumption @ 50Hz [W]220 W
Fan power output @ 50Hz [W]120 W
Fan power supply [V/Ph/Hz]230/1/50
Fan voltage @ 50Hz (max) [V] [Max]230 V
Fan voltage @ 50Hz (max) [V] [Min]230 V
Frequency [Hz]50 Hz
Height (EF000040)825.000
High value of nominal voltage at 50Hz [V]415 V
HMBP Cooling capacity [kW] (R513A/R134a)5.63 kW
HMBP Cooling capacity range [kW] (R513A/R134a)3.7 to 7 kW
In scope of WEEENo
LBP Cooling capacity range [kW] (R452A)Not available for this condition / refrigerant
Length [mm]464.0 mm
Liquid line connection [in]1/2 in
Low value of nominal voltage at 50Hz [V]380 V
Material DescriptionOP-MSXM080MLW05E
MBP Cooling capacity [kW] (R449A)8.54 kW
MBP Cooling capacity range [kW] (R22)Not available for this condition / refrigerant
MBP Cooling capacity range [kW] (R449A)8.3 to 17 kW
MCC15 A
Min fuse rating [A]20 A
Characteristic
Value
Model numberOP-MSXM080MLW05E
No. of phases (compressor)3
No. of phases (fan)1
Number of fans1
Number of phases (EF000351)3
Overload relay typeLRE21
Phase3
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
Product TypeOptyma™ Slim Pack W05
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)N,N-dimethylacetamide (CAS no. 127-19-5)
Receiver approvalCE
Receiver volume [L]6.2 L
RefrigerantsR134aR404AR407AR407FR448AR449AR452AR507AR513A
RLA9.6 A
SCIP dossier no.517dd61a-f0c7-4249-8639-17b34a9dfce2
SCIP dossier product nameOPTYMA W05
Segment usageMedium Back Pressure
Sound power @ 50Hz [db(A)]75 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]64 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]44 dBA
Suction connection size [in]7/8 in
Suitable for type of refrigerant R134a (EF013569)TRUE
Suitable for type of refrigerant R22 (EF013579)FALSE
Suitable for type of refrigerant R290 (EF013580)FALSE
Suitable for type of refrigerant R32 (EF013567)FALSE
Suitable for type of refrigerant R401a (EF013581)FALSE
Suitable for type of refrigerant R402a (EF013582)FALSE
Suitable for type of refrigerant R404a (EF013568)TRUE
Suitable for type of refrigerant R407c (EF013583)FALSE
Suitable for type of refrigerant R413a (EF013584)FALSE
Suitable for type of refrigerant R417a (EF013585)FALSE
Suitable for type of refrigerant R507 (EF013570)TRUE
TechnologyScroll
Total height [mm]825.0 mm
VersionW05
VersionDescriptionW05 : Optyma Slim Pack - Standard version
Voltage 50Hz [V]380 V
Voltage 50Hz [V] [Max]415 V
Weight (EF000167)96.00
Width (EF000008)1105.00
Width [mm]1105.00 mm

General specifications

Characteristic
Value
Gross weight96 Kilogram
Net weight77 Kilogram
Volume616.896 Liter
Characteristic
Value
EAN/UPC5702428562270
Proposition 65Cancer and Reproductive Harm