Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]5200 m³/h
Air volume (EF002618)5200
ApplicationsMBP
China RoHS complianceOut of scope
Compression method (EF013498)Scroll compressor
Compressor modelMLZ038T4
Compressor power supply [V]400/3/50
Condenser Coil Internal Volume [L]1.62 L
Condenser typeG7
Connection typeSolder
Connection voltage (EF003625)230
Contains batteriesNo
CoolselectorFilterActive models
Depth (EF000049)1520
DescriptionOP-MPXM080MLP00E
DG Indicator ProfileNot relevant for dangerous goods
Electrical codeE
EU RoHS complianceOut of scope
FamilyOptyma™ Plus
Fan blade size [mm]500.000 mm
Fan cowl/grill typeH3
Fan current @ 50Hz [A]0.96 A
Fan diameter [mm]500 mm
Fan power consumption @ 50Hz [W]190 W
Fan power output @ 50Hz [W]104 W
Fan power supply [V/Ph/Hz]230/1/50
Fan voltage @ 50Hz (max) [V] [Max]230 V
Fan voltage @ 50Hz (max) [V] [Min]230 V
Frequency [Hz]50 Hz
Height (EF000040)967.000
High value of nominal voltage at 50Hz [V]415 V
HMBP Cooling capacity [kW] (R513A/R134a)5.63 kW
HMBP Cooling capacity range [kW] (R513A/R134a)3.7 to 7 kW
In scope of WEEENo
LBP Cooling capacity range [kW] (R452A)Not available for this condition / refrigerant
Length [mm]531.0 mm
Liquid line connection [in]5/8 in
Low value of nominal voltage at 50Hz [V]380 V
LRA70 A
Material DescriptionOP-MPXM080MLP00E
MBP Cooling capacity [kW] (R449A)8.54 kW
MBP Cooling capacity range [kW] (R22)Not available for this condition / refrigerant
MBP Cooling capacity range [kW] (R449A)8.3 to 17 kW
MCC15 A
Characteristic
Value
Min fuse rating [A]20 A
Model numberOP-MPXM080MLP00E
No. of phases (compressor)3
No. of phases (fan)1
Number of fans1
Number of phases (EF000351)3
Phase3
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
Product TypeOptyma™ Plus P00
REACH Candidate List substancesLead (CAS no. 7439-92-1)N,N-dimethylacetamide (CAS no. 127-19-5)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)
Receiver approvalCE
Receiver volume [L]6.2 L
RefrigerantsR134aR404AR407AR407FR448AR449AR452AR507AR513A
RLA9.6 A
SCIP dossier no.79e44f1b-ab3b-44c1-b280-ba3435673604
SCIP dossier product nameOPTYMA P00 G7 J7
Segment usageMedium Back Pressure
Sound power @ 50Hz [db(A)]73 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]62 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]42 dBA
Suction connection size [in]7/8 in
Suitable for type of refrigerant R134a (EF013569)TRUE
Suitable for type of refrigerant R22 (EF013579)FALSE
Suitable for type of refrigerant R290 (EF013580)FALSE
Suitable for type of refrigerant R32 (EF013567)FALSE
Suitable for type of refrigerant R401a (EF013581)FALSE
Suitable for type of refrigerant R402a (EF013582)FALSE
Suitable for type of refrigerant R404a (EF013568)TRUE
Suitable for type of refrigerant R407c (EF013583)FALSE
Suitable for type of refrigerant R413a (EF013584)FALSE
Suitable for type of refrigerant R417a (EF013585)FALSE
Suitable for type of refrigerant R507 (EF013570)TRUE
TechnologyScroll
Total height [mm]965.0 mm
VersionP00
VersionDescriptionP00 : Optyma Plus - Standard version
Voltage 50Hz [V]380 V
Voltage 50Hz [V] [Max]415 V
Weight (EF000167)137.00
Width (EF000008)1406.00
Width [mm]1441.00 mm

General specifications

Characteristic
Value
Gross weight137 Kilogram
Net weight101 Kilogram
Volume1076.16 Liter
Characteristic
Value
EAN/UPC5702428564526
Proposition 65Cancer and Reproductive Harm