Product specifications

Characteristic
Value
Allowed temperature [˚C] [Min]2 °C
Application typeIndirect Heating
ApprovalCE
Capacity [kW]50.0 kW
Category nameIndirect heating substations
CE evaluatedYes
Connection direction primary and secondaryRight and top+bottom
Contain batteriesNo
Cover materialEPP
Current [A] [Max]2.0 A
Delta P primary without heat meter [bar] [Min]0.53 bar
Depth with cover [mm]482 mm
Depth without cover [mm]482 mm
DescriptionStuttgart_12.2_1xFH_MIX_plus_1xDHW_sec: Insert Energy Meter, primary right/secondary top + down, High Temperature, SV 3bar TÜV
DesignWall mounted
DG Indicator ProfileNot relevant for dangerous goods
DH connection sizeG1"
DH connection typeexternal thread
DH pipe sizeDN20
Differential pressure controllerAVQM
Differential pressure primary [bar] [Max]20 bar
Floor heating circuit - pump brandGrundfos
Floor heating circuit - pump typeUPMXL Auto 25-105 180
Flow primary [m3/h] [Max]0.74 m³/h
Flow secondary [m3/h] [Max]1.71 m³/h
HE connection sizeRp1 1/2"
HE connection typeinternal thread
HE pipe sizeDN32
Heating control typeElectronic
Characteristic
Value
Heating controller nameECL310
Heating HEX typeXB12M-1-26
Height with cover [mm]1399 mm
Height without cover [mm]1399 mm
HEX heating alloy1.4404
HEX heating brazed/gasketed materialBrazed copper
Insulation materialEPP
Manufacturer's nameDanfoss
Material DescriptionDSA1 MINI-DRB050-F1WSS_
Mixing circuit - controlHRB32-16/AMB162
Number of floor heating manifold connections1
Package depth [mm]800 mm
Package height [mm]620 mm
Package width [mm]1200 mm
PED category§ 4.3
Pressure nominal primary [bar]25 bar
Pressure nominal secondary [bar]6 bar
Pressure primary [bar] [Max]25 bar
Pressure secondary [bar] [Max]3 bar
Product groupSubstations
Product lineHeavy Duty Stations
Product TypeDSA 1 MINI
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Sensor type heatmeterdirect
Substation versionStuttgart, 12.2
Supply temperature construction [˚C]130 °C
Supply voltage [V] AC230 V
Width with cover [mm]900 mm
Width without cover [mm]900 mm

General specifications

Characteristic
Value
Gross weight70 Kilogram
Net weight50 Kilogram
Characteristic
Value
EAN/UPC5715162739990
Proposition 65Cancer and Reproductive Harm