Substations, DSP1 MAXI, Heating controller name: ECL310
004F4840
DSP1 MAXI-PD-32 HT I300
Product specifications
Characteristic | Value |
---|---|
Allowed temperature [˚C] [Min] | 2 °C |
Application type | Indirect Heating |
Approval | CE |
Category name | Indirect heating substations |
CE evaluated | Yes |
Connection direction primary and secondary | Up |
Cover material | Sheet Metal |
Cover option | Yes |
Delta P primary without heat meter [bar] [Min] | 0.61 bar |
Delta P secondary [bar] [Max] | 0.23 bar |
Depth with cover [mm] | 1150 mm |
Depth without cover [mm] | 1150 mm |
Description | DSP1 MAXI-PD-32 HT I300 |
Design | standing |
DG Indicator Profile | Not relevant for dangerous goods |
DH connection size | 60,3 mm |
DH connection type | welded |
DH pipe size | DN50 |
Differential pressure primary [bar] [Max] | 16 bar |
Fitting piece | Insert primary return |
Flow primary [m3/h] [Max] | 10.00 m³/h |
Flow secondary [m3/h] [Max] | 19.30 m³/h |
HE connection size | DN65 |
HE connection type | flange |
HE pipe size | DN65 |
Heating control type | Electronic |
Heating controller name | ECL310 |
Height with cover [mm] | 1670 mm |
Characteristic | Value |
---|---|
Height without cover [mm] | 1670 mm |
HEX heating alloy | 1.4404 |
HEX heating brazing material | Copper |
HEX heating type | Brazed |
In scope of WEEE and contain batteries | No |
Insulation material | PU Hard Foam |
Manufacturer's name | Danfoss |
Material Description | DSP1 MAXI-PD-32 HT I300 |
Number of floor heating manifold connections | 1 |
Number of heating manifold connections [loops] [Max] | 1 |
Package depth [mm] | 800 mm |
Package height [mm] | 1900 mm |
Package width [mm] | 1200 mm |
PED category | II |
Pressure nominal primary [bar] | 25 bar |
Pressure nominal secondary [bar] | 6 bar |
Pressure primary [bar] [Max] | 22 bar |
Pressure secondary [bar] [Max] | 3 bar |
Product group | Substations |
Product line | Heavy Duty Stations |
Product Type | DSP1 MAXI |
REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
Sensor type heatmeter | muff 1/2" |
Substation version | 32 HT I300 |
Supply temperature construction [˚C] | 140 °C |
Supply voltage [V] AC | 230 V |
Width with cover [mm] | 750 mm |
Width without cover [mm] | 750 mm |
General specifications
Characteristic | Value |
---|---|
Gross weight | 147 Kilogram |
Net weight | 147 Kilogram |
Characteristic | Value |
---|---|
EAN | 5715162746660 |
Proposition 65 | Cancer and Reproductive Harm |