Substations, DSA 1 MINI, Biomass, HT_IN_AT, 15.0 kW
146B5425
BIOMASS_HT_IN_AT: Insert Energy Meter, primary bottom/secondary bottom, High Temperature, PN 16, SV 3bar TÜV
Product specifications
Characteristic | Value |
---|---|
Allowed temperature [˚C] [Min] | 2 °C |
Application type | Indirect Heating |
Approval | CE |
Capacity [kW] | 15.0 kW |
Category name | Indirect heating substations |
CE evaluated | Yes |
Connection direction primary and secondary | bottom |
Cover material | EPP |
Current [A] [Max] | 2.0 A |
Delta P primary without heat meter [bar] [Min] | 0.49 bar |
Delta P secondary [bar] [Max] | 0.19 bar |
Depth with cover [mm] | 482 mm |
Depth without cover [mm] | 482 mm |
Description | BIOMASS_HT_IN_AT: Insert Energy Meter, primary bottom/secondary bottom, High Temperature, PN 16, SV 3bar TÜV |
Design | Wall mounted |
DG Indicator Profile | Not relevant for dangerous goods |
DH connection size | G1" |
DH connection type | external thread |
DH pipe size | DN20 |
Differential pressure controller | AVQM |
Differential pressure primary [bar] [Max] | 12 bar |
Fitting piece | Insert primary return |
Flow primary [m3/h] [Max] | 0.40 m³/h |
Flow secondary [m3/h] [Max] | 0.90 m³/h |
HE connection size | Rp1" |
HE connection type | internal thread |
HE pipe size | DN25 |
Heating control type | Electronic |
Heating controller name | ECL310 |
Characteristic | Value |
---|---|
Heating HEX type | XB12H-1-16 |
Height with cover [mm] | 856 mm |
Height without cover [mm] | 856 mm |
HEX heating alloy | 1.4404 |
HEX heating brazing material | Copper |
HEX heating type | Brazed |
In scope of WEEE and contain batteries | No |
Insulation material | EPP |
Manufacturer's name | Danfoss |
Material Description | DSA1 MINI-DUU015-HI110AT |
Number of heating manifold connections [loops] [Max] | 1 |
Package depth [mm] | 800 mm |
Package height [mm] | 620 mm |
Package width [mm] | 1200 mm |
PED category | § 4.3 |
Pressure nominal primary [bar] | 16 bar |
Pressure nominal secondary [bar] | 6 bar |
Pressure primary [bar] [Max] | 16 bar |
Pressure secondary [bar] [Max] | 3 bar |
Product group | Substations |
Product line | Heavy Duty Stations |
Product Type | DSA 1 MINI |
REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
Sensor type heatmeter | |
Substation version | Biomass, HT_IN_AT |
Supply temperature construction [˚C] | 120 °C |
Supply voltage [V] AC | 230 V |
Width with cover [mm] | 680 mm |
Width without cover [mm] | 680 mm |
General specifications
Characteristic | Value |
---|---|
Gross weight | 70 Kilogram |
Net weight | 50 Kilogram |
Characteristic | Value |
---|---|
EAN | 5715162742570 |
Proposition 65 | Cancer and Reproductive Harm |