Danfoss logo
DSA WALL POLAND

Substations, DSA2 WALL, 2F-1, 60 kW, Heating controller name: ECL310, DHW controller name: AVTQ, DHW circulation: Yes

148L5010

DSA WALL 2F-1

Product specifications

Characteristic
Value
Allowed temperature [˚C] [Min]2 °C
Application typeIndirect heating & Instantaneous DHW
ApprovalCE
Capacity [kW]60.0 kW
Category nameIndirect heating substations
CE evaluatedYes
Circulation connection sizeDN15
Circulation connection typeinternal thread
Circulation pipe sizeDN15
Connection direction primary and secondaryLeft / Right
Contain batteriesNo
Cover materialWhite-lacquered steel sheet
Cover optionNo
Delta P primary without heat meter [bar] [Min]0.47 bar
Depth with cover [mm]650 mm
Depth without cover [mm]650 mm
DescriptionDSA WALL 2F-1
DesignWall mounted
DG Indicator ProfileNot relevant for dangerous goods
DH connection sizeDN25
DH connection typeexternal thread
DH pipe sizeDN25
DHW circulationYes
DHW circulation pump brandGrundfos
DHW circulation pump typeUPS 25-60 N 180
DHW connection sizeDN20
DHW connection typeinternal thread
DHW Control typeThermostatic
DHW controller nameAVTQ
DHW HEX typeXB37M-20
DHW pipe sizeDN20
Differential pressure primary [bar] [Max]12 bar
Flow primary [m3/h] [Max]1.99 m³/h
HE connection sizeDN25
Characteristic
Value
HE connection typeinternal thread
HE pipe sizeDN20
Heating control typeElectronic
Heating controller nameECL310
Heating HEX typeXB37L-10
Heating pump brandGrundfos
Heating pump typeUPM3 Auto L
Height with cover [mm]1200 mm
Height without cover [mm]1200 mm
HEX DHW alloy1.4404
HEX DHW brazed/gasketed materialBrazed copper
HEX heating alloy1.4404
HEX heating brazed/gasketed materialBrazed copper
Insulation materialEPP
Manufacturer's nameDanfoss
Material DescriptionDSA 2F-1 WALL
Number of households [Max]2
Number of households [Min]1
Package depth [mm]800 mm
Package height [mm]800 mm
Package width [mm]1200 mm
PED category§ 4.3
Pressure nominal primary [bar]16 bar
Pressure nominal secondary [bar]10 bar
Pressure primary [bar] [Max]16 bar
Pressure secondary [bar] [Max]10 bar
Product groupSubstations
Product lineHeavy Duty Stations
Product TypeDSA2 WALL
Substation version2F-1
Supply temperature construction [˚C]130 °C
Supply voltage [V] AC230 V
Width with cover [mm]650 mm
Width without cover [mm]800 mm

General specifications

Characteristic
Value
Gross weight80 Kilogram
Net weight60 Kilogram
Characteristic
Value
EAN5715162738955