Danfoss logo
AFA2 actuator

AFPA 2, PN 16, 1 bar - 3 bar, 160 cm²

003G5691

Differential pressure relief actuator

Product specifications

Characteristic
Value
Actuator diaphragm materialEPDM (Rolling, fibre enforced)
Actuator size [cm²]160 cm²
ApplicationDistrict heating and cooling
Body materialSteel, mat. No. 1.0345, zinc plated
China RoHS complianceOut of scope
Contain batteriesNo
DG Indicator ProfileNot relevant for dangerous goods
DescriptionDifferential pressure relief actuator
Diameter [mm] [Max]250 mm
Diameter [mm] [Min]65 mm
Differential pressure setting [bar] [Max]3.00 bar
Differential pressure setting [bar] [Min]1.00 bar
EU RoHS complianceOut of scope
Flow controlNo
Flow limitationNo
FunctionDiff. press. relief controller
Material DescriptionAFPA 2 PN16 1-3 160cm2red
Characteristic
Value
Media pH [Max]10
Media pH [Min]7
Media temperature [°C] [Max]150 °C
Media temperature [°C] [Min]2 °C
Medium alternativeGlycolic water up to 30%
Mounting versionBypass
Operating pressure [bar] [Max]16 bar
Permissible mediaDistrict heating/cooling circulation water
Pressure classPN 16
Pressure controllerDifferential pressure relief controller
Pressure nominal [bar]16 bar
Product TypeAFPA 2
Product groupActuators - Pressure Flow
Product lineDistrict Energy Controls
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Setting TypeAdjustable

General specifications

Characteristic
Value
Gross weight14.789 Kilogram
Net weight13.5 Kilogram
Volume52.304 Liter
Characteristic
Value
EAN/UPC5715162292648
Proposition 65Cancer and Reproductive Harm