Danfoss logo
Thermostatic expansion valve, TCBE_068U4593

Thermostatic expansion valve, TCBE, R407C

068U4506

Temperature range [°C]: -40 - 10, MOP Point [°C]: 15, Orifice capacities [kW]: 28.50, Orifice capacities [TR]: 8.10, Pressure equalization: Externally equalized

Product specifications

Characteristic
Value
ApprovalEACLLC CDC TYSKUL
Body materialStainless steel
Capillary tube length [in]35.0 in
Capillary tube length [mm]900 mm
China RoHS complianceYes exceed limitations
Connection materialBi-metal: Steel/copper
Contain batteriesNo
DG Indicator ProfileOther Dangerous Goods
DirectionStraightway
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(a)6(c)
Equalization connection typeSolder, ODF
Equalization size [mm]6 mm
Flow directionSingle-flow
Flow direction indicatorLaser engraved 1-way arrow
Fluid Group2
Identical product068U4263
Inlet connection typeSolder, ODF
Inlet size [mm]12.00 mm
MOP Point [psig]MOP 95
MOP Point [°C]15 °C
MOP Point [°F]60 °F
Material DescriptionTCBE/s Therm. exp. valve I/45
Max. Working Pressure [bar]45.5 bar
Max. Working Pressure [psig]660 psig
Orifice capacities [TR]8.10 TR
Orifice capacities [kW]28.50 kW
Orifice size3
Characteristic
Value
Outlet connection typeSolder, ODF
Outlet size [mm]16.00 mm
PED categoryArt. 4, par. 3
Packing formatIndustrial pack
Parts includedBulb strap
Pressure equalizationExternally equalized
Product TypeTCBE
Product accessoriesTXV accessories
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameThermostatic expansion valve
Quantity per packing format45 pc
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Rated cap. cond. Range N [IMP]OS=7.2 ºFtcond=100 ºFtevap=40 ºFtliq=98 ºF
Rated cap. cond. Range N [SI]OS=4Ktcond=38 ºCtevap=4.4 ºCtliq=37 ºC
RefrigerantsR407C
SCIP dossier no.07795324-de66-41b2-9761-afe6640e393c
SCIP dossier product nameTU/TC - Thermostatic expansion valve
ServiceableNo
Static Superheat (SS) [°C]4.00 °C
Static Superheat (SS) [°F]7.20 °F
Superheat settingAdjustable
Temperature range [°C] [max]10 °C
Temperature range [°C] [min]-40 °C
Temperature range [°F] [max]50 °F
Temperature range [°F] [min]-40 °F
UL approved refrigerantsR407C
UL evaluatedYes

General specifications

Characteristic
Value
Gross weight0.204 Kilogram
Net weight0.188 Kilogram
Characteristic
Value
EAN/UPC5702428032308
Proposition 65Cancer and Reproductive Harm