Danfoss logo
TUB SW_068U2676, 068U3382, 068U3700, 068U3939

Thermostatic expansion valve, TUB, R404A/R507A

068U3814

Temperature range [°C]: -40 - 10, Orifice capacities [kW]: 1.10, Orifice capacities [TR]: 0.32, Pressure equalization: Internally equalized
The product is no longer available for purchase, but you can still find information about it, including service manuals, drawing etc.

If you're looking for a similar product, you can check out other options within the same product type by visiting the product type page.: TU / TC

Product specifications

Characteristic
Value
ApprovalEACLLC CDC TYSKUL
Body materialStainless steel
Capillary tube length [in]31.0 in
Capillary tube length [mm]800 mm
China RoHS complianceYes exceed limitations
Connection materialBi-metal: Steel/copper
Contain batteriesNo
DG Indicator ProfileOther Dangerous Goods
DirectionStraightway
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(a)6(c)
Flow directionSingle-flow
Flow direction indicatorLaser engraved 1-way arrow
Fluid Group2
Identical product068U2751
Inlet connection typeSolder, ODF
Inlet size [in]1/4 in
Material DescriptionTUB/s Therm. exp. valve I/45
Max. Working Pressure [bar]34.0 bar
Max. Working Pressure [psig]500 psig
Orifice capacities [TR]0.32 TR
Orifice capacities [kW]1.10 kW
Orifice size3
Outlet connection typeSolder, ODF
Outlet size [in]3/8 in
PED categoryArt. 4, par. 3
Characteristic
Value
Packing formatIndustrial pack
Parts includedBulb strap
Pressure equalizationInternally equalized
Product TypeTUB
Product accessoriesTXV accessories
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameThermostatic expansion valve
Quantity per packing format45 pc
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Rated cap. cond. Range N [IMP]OS=7.2 ºFtcond=100 ºFtevap=40 ºFtliq=98 ºF
Rated cap. cond. Range N [SI]OS=4Ktcond=38 ºCtevap=4.4 ºCtliq=37 ºC
RefrigerantsR404A/R507A
SCIP dossier no.07795324-de66-41b2-9761-afe6640e393c
SCIP dossier product nameTU/TC - Thermostatic expansion valve
ServiceableNo
Static Superheat (SS) [°C]4.00 °C
Static Superheat (SS) [°F]7.20 °F
Superheat settingAdjustable
Temperature range [°C] [max]10 °C
Temperature range [°C] [min]-40 °C
Temperature range [°F] [max]50 °F
Temperature range [°F] [min]-40 °F
UL approved refrigerantsR404AR507A
UL evaluatedYes

General specifications

Characteristic
Value
Gross weight0.162 Kilogram
Net weight0.149 Kilogram
Characteristic
Value
EAN/UPC5702428974394
Proposition 65Cancer and Reproductive Harm