Orifice for expansion valve, ORF, R407A; R134a/R513A; R23; R455A; R407C; R236fa; R452A; R454C; R404A/R507A; R1234yf; R448A; R22/R407C; R449A
068-2096
Temperature range [°C]: -40 - 10
Product specifications
Characteristic | Value |
---|---|
Approval | EACLLC CDC TYSK |
China RoHS compliance | Out of scope |
Design | Solder Adapter only |
DG Indicator Profile | Not relevant for dangerous goods |
EU RoHS compliance | Yes with exemptions |
EU RoHS exemption clause | 6(a)6(c) |
Fluid Group | 1 |
In scope of WEEE and contain batteries | No |
Material Description | Orifice No 06 for T/TE 2 |
Orifice size | 06 |
Packing format | Multi pack |
Parts Program name | T2/TE2 |
PED category | Art. 4, par. 3 |
Product accessories | TXV accessories |
Product group | Expansion valves |
Product line | Air Conditioning and Commercial Refrigeration |
Product name | Orifice for expansion valve |
Product Type | ORF |
Quantity per packing format | 25 pc |
Rated cap. cond. Range N [IMP] | tcond=100 ºFtevap=40 ºFtliq=98 ºF |
Rated cap. cond. Range N [SI] | tcond=38 ºCtevap=4.4 ºCtliq=37 ºC |
Rated cap. R1234yf, N [kW] | 7.32 kW |
Rated cap. R1234yf, N [TR] | 2.08 TR |
Rated cap. R134a, Range N [kW] | 10.10 kW |
Rated cap. R134a, Range N [TR] | 2.90 TR |
Rated cap. R22, Range B [kW] | 8.70 kW |
Rated cap. R22, Range B [TR] | 2.50 TR |
Rated cap. R22, Range N [kW] | 19.70 kW |
Rated cap. R22, Range N [TR] | 5.60 TR |
Characteristic | Value |
---|---|
Rated cap. R404A, Range B [kW] | 6.90 kW |
Rated cap. R404A, Range B [TR] | 2.00 TR |
Rated cap. R404A, Range N [kW] | 15.50 kW |
Rated cap. R404A, Range N [TR] | 4.40 TR |
Rated cap. R407C, Range N [kW] | 19.70 kW |
Rated cap. R407C, Range N [TR] | 5.60 TR |
Rated cap. R452A, Range N [kW] | 15.78 kW |
Rated cap. R452A, Range N [TR] | 4.49 TR |
Rated cap. R454C, Range N [kW] | 14.78 kW |
Rated cap. R454C, Range N [TR] | 4.20 TR |
Rated cap. R455A, Range N [kW] | 18.35 kW |
Rated cap. R455A, Range N [TR] | 5.22 TR |
Rated cap. R507, Range B [kW] | 6.90 kW |
Rated cap. R507, Range B [TR] | 2.00 TR |
Rated cap. R507, Range N [kW] | 15.50 kW |
Rated cap. R507, Range N [TR] | 4.40 TR |
Rated cap. R513A, Range N [kW] | 8.60 kW |
Rated cap. R513A, Range N [TR] | 2.50 TR |
REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
Refrigerants | R1234yfR134a/R513AR22/R407CR23R236faR404A/R507AR407AR407CR448AR449AR452AR454CR455A |
SCIP dossier no. | c164ed45-f10d-4d73-9eae-355ccb479f4b |
SCIP dossier product name | T2 /TE2 - Thermostatic Expansion Valve |
Serviceable | No |
Temperature range [°C] [max] | 10 °C |
Temperature range [°C] [min] | -40 °C |
Temperature range [°F] [max] | 50 °F |
Temperature range [°F] [min] | -40 °F |
UK RoHS compliance | Out of scope |
Used for product | T 2TE 2 |
General specifications
Characteristic | Value |
---|---|
Gross weight | 13.375 Gram |
Net weight | 9 Gram |
Volume | 0.017 Liter |
Characteristic | Value |
---|---|
EAN | 5702422099956 |
Proposition 65 | Cancer and Reproductive Harm |