Danfoss logo
T2 orifice

Orifice for expansion valve, ORF, R407A; R134a/R513A; R23; R455A; R407C; R236fa; R452A; R454C; R404A/R507A; R1234yf; R448A; R22/R407C; R449A

068-2010

Temperature range [°C]: -40 - 10

Product specifications

Characteristic
Value
ApprovalEACLLC CDC TYSK
China RoHS complianceOut of scope
DesignSAE flare only
DG Indicator ProfileNot relevant for dangerous goods
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(a)6(c)
Fluid Group1
In scope of WEEE and contain batteriesNo
Material DescriptionOrifice No 01 for T/TE 2
Orifice size01
Packing formatMulti pack
Parts Program nameT2/TE2
PED categoryArt. 4, par. 3
Product accessoriesTXV accessories
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameOrifice for expansion valve
Product TypeORF
Quantity per packing format25 pc
Rated cap. cond. Range N [IMP]tcond=100 ºFtevap=40 ºFtliq=98 ºF
Rated cap. cond. Range N [SI]tcond=38 ºCtevap=4.4 ºCtliq=37 ºC
Rated cap. R1234yf, N [kW]1.50 kW
Rated cap. R1234yf, N [TR]0.43 TR
Rated cap. R134a, Range N [kW]2.10 kW
Rated cap. R134a, Range N [TR]0.59 TR
Rated cap. R22, Range B [kW]2.00 kW
Rated cap. R22, Range B [TR]0.57 TR
Rated cap. R22, Range N [kW]3.50 kW
Rated cap. R22, Range N [TR]1.00 TR
Characteristic
Value
Rated cap. R404A, Range B [kW]1.60 kW
Rated cap. R404A, Range B [TR]0.46 TR
Rated cap. R404A, Range N [kW]2.60 kW
Rated cap. R404A, Range N [TR]0.75 TR
Rated cap. R407C, Range N [kW]3.50 kW
Rated cap. R407C, Range N [TR]1.00 TR
Rated cap. R452A, Range N [kW]2.74 kW
Rated cap. R452A, Range N [TR]0.78 TR
Rated cap. R454C, Range N [kW]2.78 kW
Rated cap. R454C, Range N [TR]0.79 TR
Rated cap. R455A, Range N [kW]3.28 kW
Rated cap. R455A, Range N [TR]0.93 TR
Rated cap. R507, Range B [kW]1.60 kW
Rated cap. R507, Range B [TR]0.46 TR
Rated cap. R507, Range N [kW]2.60 kW
Rated cap. R507, Range N [TR]0.75 TR
Rated cap. R513A, Range N [kW]1.80 kW
Rated cap. R513A, Range N [TR]0.51 TR
REACH Candidate List substancesLead (CAS no. 7439-92-1)
RefrigerantsR1234yfR134a/R513AR22/R407CR23R236faR404A/R507AR407AR407CR448AR449AR452AR454CR455A
SCIP dossier no.c164ed45-f10d-4d73-9eae-355ccb479f4b
SCIP dossier product nameT2 /TE2 - Thermostatic Expansion Valve
ServiceableNo
Temperature range [°C] [max]10 °C
Temperature range [°C] [min]-40 °C
Temperature range [°F] [max]50 °F
Temperature range [°F] [min]-40 °F
UK RoHS complianceOut of scope
Used for productT 2TE 2

General specifications

Characteristic
Value
Gross weight0.018 Kilogram
Net weight0.013 Kilogram
Volume0.017 Liter
Characteristic
Value
EAN5702422014799
Proposition 65Cancer and Reproductive Harm