Condensing pressure regulator, KVR 15
034L0097
Inlet connection type: Solder, ODF, Outlet connection type: Solder, ODF, Max. Working Pressure [bar]: 28.0
Product specifications
Characteristic | Value |
---|---|
Approval | C UL US LISTEDEACLLC CDC TYSKRoHSRoHS China |
Approval file name | REFRIGERANT VALVE 53R0 |
China RoHS compliance | Yes |
DG Indicator Profile | Not relevant for dangerous goods |
Equipment | Schrader valve access port |
EU RoHS compliance | Yes |
EU RoHS exemption clause | No |
Factory setting [psig] | 145.0 psig |
Flow direction indicator | Engraved 1-way arrow |
Identical product | 034L1097 |
In scope of WEEE and contain batteries | No |
Inlet connection type | Solder, ODF |
Inlet size [in] | 5/8 in |
Inlet size [mm] | 16.00 mm |
Lubricants compatibility | Oilfree applications |
Material Description | KVR 15 Condensing Pres. Reg. M/12 |
Max. test pressure [bar] | 31.0 bar |
Max. test pressure [psig] | 450.0 psig |
Max. Working Pressure [bar] | 28.0 bar |
Max. Working Pressure [psig] | 406 psig |
Medium temperature range [°C] [max] | 130 °C |
Medium temperature range [°C] [min] | -45 °C |
Medium temperature range [°F] [max] | 266 °F |
Medium temperature range [°F] [min] | -49 °F |
Oil free refrigerants | R1234ze(E)R513A |
Other RoHS documentation | EAEU RoHS |
Outlet connection type | Solder, ODF |
Outlet size [in] | 5/8 in |
Outlet size [mm] | 16.00 mm |
P band max. [bar] | 6.2 bar |
P band max. [psi] | 90.0 psi |
Packing format | Multi pack |
Product accessories | No |
Product group | Press. and temp. regul. valves |
Characteristic | Value |
---|---|
Product line | Air Conditioning and Commercial Refrigeration |
Product name | Condensing pressure regulator |
Product Type | KVR 15 |
Quantity per packing format | 12 pc |
Rated cap. conditions [IMP] | Delta p hotgas=6 psiDelta p liquid=3 psitcond=110 °Ftevap=40 °F |
Rated cap. conditions [SI] | Delta p hotgas=0.4 barDelta p liquid=0.2 barOffset=3 bartcond=30 °Ctevap=-10 °C |
Rated cap. R134a, Hot gas [kW] | 11.50 kW |
Rated cap. R134a, Hot gas [TR] | 3.03 TR |
Rated cap. R22, Hot gas [kW] | 13.20 kW |
Rated cap. R22, Hot gas [TR] | 4.13 TR |
Rated cap. R404A/R507A [kW] | 36.60 kW |
Rated cap. R404A/R507A [TR] | 8.20 TR |
Rated cap. R407C, Hot gas [kW] | 14.30 kW |
Rated cap. R407C, Hot gas [TR] | 4.50 TR |
Rated cap.R404A/R507,Hot gas[k | 12.00 kW |
Rated cap.R404A/R507,Hot gas[T | 3.27 TR |
Rated capacity R134a [kW] | 47.30 kW |
Rated capacity R134a [TR] | 11.80 TR |
Rated capacity R22 [kW] | 50.40 kW |
Rated capacity R22 [TR] | 12.70 TR |
Rated capacity R407C [kW] | 54.40 kW |
Rated capacity R407C [TR] | 13.80 TR |
REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
Refrigerants | R1234yfR1234ze(E)R1270R134aR22R290R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR454AR454CR455AR507AR513AR515BR516AR600R600a |
Regulation range [bar] [max] | 17.5 bar |
Regulation range [bar] [min] | 5.0 bar |
Regulation range [psig] Pe [max] | 254.00 psig |
Regulation range [psig] Pe [min] | 73.00 psig |
SCIP dossier no. | 842c526f-b213-4baa-869c-a91bb999a318 |
Serviceable | KV valves spare parts |
UK RoHS compliance | Out of scope |
UL approved refrigerants | R134aR22R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR507AR513AR515BR516A |
UL evaluated | Yes |
General specifications
Characteristic | Value |
---|---|
Gross weight | 0.392 Kilogram |
Net weight | 0.355 Kilogram |
Volume | 1.18 Liter |
Characteristic | Value |
---|---|
EAN | 5702428411585 |
Proposition 65 | Cancer and Reproductive Harm |