Danfoss logo
KVR Condensing pressure regulator (flare), size 12

Condensing pressure regulator, KVR 15

034L0092

Inlet connection type: Flare, Outlet connection type: Flare, Max. Working Pressure [bar]: 28.0

Product specifications

Characteristic
Value
ApprovalC UL US LISTEDEACLLC CDC TYSKRoHSRoHS China
Approval file nameREFRIGERANT VALVE 53R0
Basic Data Text TemplateПоддержание давления в конденсаторевсе фреоны(R22 -10/+30 28.1кВт)5/8 под вальцовку
China RoHS complianceYes
Contain batteriesNo
DG Indicator ProfileNot relevant for dangerous goods
EU RoHS complianceYes
EU RoHS exemption clauseNo
EquipmentSchrader valve access port
Factory setting [psig]145.0 psig
Flow direction indicatorEngraved 1-way arrow
Inlet connection typeFlare
Inlet size [in]5/8 in
Inlet size [mm]16.00 mm
Lubricants compatibilityOilfree applications
Material DescriptionKVR 15 Condensing Pres. Reg. M/12
Max. Working Pressure [bar]28.0 bar
Max. Working Pressure [psig]406 psig
Max. test pressure [bar]31.0 bar
Max. test pressure [psig]450.0 psig
Medium temperature range [°C] [max]130 °C
Medium temperature range [°C] [min]-45 °C
Medium temperature range [°F] [max]266 °F
Medium temperature range [°F] [min]-49 °F
Oil free refrigerantsR1234ze(E)R513A
Other RoHS documentationEAEU RoHS
Outlet connection typeFlare
Outlet size [in]5/8 in
Outlet size [mm]16.00 mm
P band max. [bar]6.2 bar
P band max. [psi]90.0 psi
Packing formatMulti pack
Product TypeKVR 15
Characteristic
Value
Product accessoriesNo
Product groupPress. and temp. regul. valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameCondensing pressure regulator
Quantity per packing format12 pc
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Rated cap. R134a, Hot gas [TR]3.03 TR
Rated cap. R134a, Hot gas [kW]11.50 kW
Rated cap. R22, Hot gas [TR]4.13 TR
Rated cap. R22, Hot gas [kW]13.20 kW
Rated cap. R404A/R507A [TR]8.20 TR
Rated cap. R404A/R507A [kW]36.60 kW
Rated cap. R407C, Hot gas [TR]4.50 TR
Rated cap. R407C, Hot gas [kW]14.30 kW
Rated cap. conditions [IMP]Delta p hotgas=6 psiDelta p liquid=3 psitcond=110 °Ftevap=40 °F
Rated cap. conditions [SI]Delta p hotgas=0.4 barDelta p liquid=0.2 barOffset=3 bartcond=30 °Ctevap=-10 °C
Rated cap.R404A/R507,Hot gas[T3.27 TR
Rated cap.R404A/R507,Hot gas[k12.00 kW
Rated capacity R134a [TR]11.80 TR
Rated capacity R134a [kW]47.30 kW
Rated capacity R22 [TR]12.70 TR
Rated capacity R22 [kW]50.40 kW
Rated capacity R407C [TR]13.80 TR
Rated capacity R407C [kW]54.40 kW
RefrigerantsR1234yfR1234ze(E)R134aR22R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR454AR454CR455AR507AR513AR515BR516A
Regulation range [bar] [max]17.5 bar
Regulation range [bar] [min]5.0 bar
Regulation range [psig] Pe [max]254.00 psig
Regulation range [psig] Pe [min]73.00 psig
SCIP dossier no.842c526f-b213-4baa-869c-a91bb999a318
ServiceableKV valves spare parts
UL approved refrigerantsR134aR22R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR507AR513AR515BR516A
UL evaluatedYes

General specifications

Characteristic
Value
Gross weight0.5 Kilogram
Net weight0.455 Kilogram
Characteristic
Value
EAN/UPC5702428411639
Proposition 65Cancer and Reproductive Harm