Evaporator pressure regulator, KVP 28
034L1076
Inlet size [in]: 1 1/8 in, Outlet size [in]: 1 1/8 in, Inlet connection type: Solder, ODF, Outlet connection type: Solder, ODF, Kv value [m³/h]: 8.000, Max. Working Pressure [bar]: 18.0
Product specifications
Characteristic | Value |
---|---|
Approval | C UL US LISTEDEACLLC CDC TYSKRoHSRoHS China |
Approval file name | REFRIGERANT VALVE 53R0 |
China RoHS compliance | Yes |
Cv value [gal/min] | 9.250 gal/min |
DG Indicator Profile | Not relevant for dangerous goods |
Equipment | Schrader valve access port |
EU RoHS compliance | Yes |
EU RoHS exemption clause | No |
Factory setting [psig] | 29.0 psig |
Flow direction indicator | Engraved 1-way arrow |
Identical product | 034L0026 |
In scope of WEEE and contain batteries | No |
Inlet connection type | Solder, ODF |
Inlet size [in] | 1 1/8 in |
Kv value [m³/h] | 8.000 m³/h |
Kv value note | AT MAX P-BAND |
Lubricants compatibility | Oilfree applications |
Material Description | KVP 28 Evaporator Pres. Reg. I/7 |
Max. test pressure [bar] | 19.8 bar |
Max. test pressure [psig] | 286.0 psig |
Max. Working Pressure [bar] | 18.0 bar |
Max. Working Pressure [psig] | 260 psig |
Medium temperature range [°C] [max] | 130 °C |
Medium temperature range [°C] [min] | -45 °C |
Medium temperature range [°F] [max] | 266 °F |
Medium temperature range [°F] [min] | -49 °F |
Oil free refrigerants | R1234ze(E)R513A |
Other RoHS documentation | EAEU RoHS |
Outlet connection type | Solder, ODF |
Characteristic | Value |
---|---|
Outlet size [in] | 1 1/8 in |
P band max. [bar] | 2.8 bar |
P band max. [psi] | 40.6 psi |
Packing format | Industrial pack |
Product accessories | No |
Product group | Press. and temp. regul. valves |
Product line | Air Conditioning and Commercial Refrigeration |
Product name | Evaporator pressure regulator |
Product Type | KVP 28 |
Quantity per packing format | 7 pc |
Rated cap. R404A/R507A [kW] | 7.70 kW |
Rated cap. R404A/R507A [TR] | 2.40 TR |
Rated capacity R134a [kW] | 6.10 kW |
Rated capacity R134a [TR] | 1.90 TR |
Rated capacity R22 [kW] | 8.60 kW |
Rated capacity R22 [TR] | 2.80 TR |
Rated capacity R407C [kW] | 7.90 kW |
Rated capacity R407C [TR] | 2.60 TR |
REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
Refrigerants | R134aR22R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR454AR454CR455AR507AR513AR515BR516A |
Regulation range [bar] [max] | 5.5 bar |
Regulation range [bar] [min] | 0.0 bar |
Regulation range [psig] Pe [max] | 80.00 psig |
Regulation range [psig] Pe [min] | 0.00 psig |
SCIP dossier no. | 842c526f-b213-4baa-869c-a91bb999a318 |
Serviceable | KV valves spare parts |
UK RoHS compliance | Out of scope |
UL approved refrigerants | R134aR22R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR507AR513AR515BR516A |
UL evaluated | Yes |
General specifications
Characteristic | Value |
---|---|
Gross weight | 0.979 Kilogram |
Net weight | 0.895 Kilogram |
Volume | 3.213 Liter |
Characteristic | Value |
---|---|
EAN | 5702428410748 |
Proposition 65 | Cancer and Reproductive Harm |