Danfoss logo
KVL Crankcase pressure regulator (flare), size 12

Crankcase pressure regulator, KVL 15

034L0042

Inlet connection type: Flare, Outlet connection type: Flare, Kv value [m³/h]: 3.200, Max. Working Pressure [bar]: 18.0

Product specifications

Characteristic
Value
ApprovalC UL US LISTEDEACLLC CDC TYSKRoHSRoHS China
Approval file nameREFRIGERANT VALVE 53R0
China RoHS complianceYes
Cv value [gal/min]3.700 gal/min
DG Indicator ProfileNot relevant for dangerous goods
EU RoHS complianceYes
EU RoHS exemption clauseNo
Factory setting [psig]29.0 psig
Flow direction indicatorEngraved 1-way arrow
Identical product034L1242
In scope of WEEE and contain batteriesNo
Inlet connection typeFlare
Inlet size [in]5/8 in
Inlet size [mm]16.00 mm
Kv value [m³/h]3.200 m³/h
Lubricants compatibilityOilfree applications
Material DescriptionKVL 15 Crankcase Pres. Reg. M/12
Max. test pressure [bar]19.8 bar
Max. test pressure [psig]286.0 psig
Max. Working Pressure [bar]18.0 bar
Max. Working Pressure [psig]260 psig
Medium temperature range [°C] [max]130 °C
Medium temperature range [°C] [min]-60 °C
Medium temperature range [°F] [max]266 °F
Medium temperature range [°F] [min]-76 °F
Oil free refrigerantsR1234ze(E)R513A
Other RoHS documentationEAEU RoHS
Outlet connection typeFlare
Outlet size [in]5/8 in
Characteristic
Value
Outlet size [mm]16.00 mm
P band max. [bar]2.0 bar
P band max. [psi]29.0 psi
Packing formatMulti pack
Product accessoriesNo
Product groupPress. and temp. regul. valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameCrankcase pressure regulator
Product TypeKVL 15
Quantity per packing format12 pc
Rated cap. R404A/R507A [kW]6.30 kW
Rated cap. R404A/R507A [TR]1.00 TR
Rated capacity R134a [kW]5.30 kW
Rated capacity R134a [TR]0.80 TR
Rated capacity R22 [kW]7.10 kW
Rated capacity R22 [TR]1.20 TR
Rated capacity R407C [kW]6.50 kW
Rated capacity R407C [TR]1.10 TR
REACH Candidate List substancesLead (CAS no. 7439-92-1)
RefrigerantsR1234yfR1234ze(E)R134aR22R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR454AR454CR455AR507AR513AR515BR516A
Regulation range [bar] [max]6.0 bar
Regulation range [bar] [min]0.2 bar
Regulation range [psig] Pe [max]87.00 psig
Regulation range [psig] Pe [min]3.00 psig
SCIP dossier no.842c526f-b213-4baa-869c-a91bb999a318
ServiceableKV valves spare parts
UK RoHS complianceOut of scope
UL approved refrigerantsR134aR22R404AR407AR407CR407FR407HR422BR422DR448AR449AR449BR450AR452AR507AR513AR515BR516A
UL evaluatedYes

General specifications

Characteristic
Value
Gross weight0.468 Kilogram
Net weight0.404 Kilogram
Volume1.18 Liter
Characteristic
Value
EAN5702428411776
Proposition 65Cancer and Reproductive Harm