Danfoss logo
KP62 Thermostat, WEB060L8017

Thermostat, KP62

060L110666

Temperature range [°C]: -30 - 15, Reset function: Auto, Contact function: SPDT, Sensor type: Room sensor, Enclosure rating IP: IP30

Product specifications

Characteristic
Value
Amb. Temp. Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalBVCCCCEDNVEACGLLLC CDC EURO-TYSKLRLVDRINARMRSRoHS Chinac UL us UL873, CS C22.2
CE evaluatedYes
Charge typeVapour
China RoHS complianceYes
Contact functionSPDT
Contact ratingAC15=10 A, 400 VAC1=16 A, 400 VAC3=16 A, 400 VDC13=12 W, 220 VLR=112 A, 400 V
Contain batteriesNo
DG Indicator ProfileOther Dangerous Goods
Diff. @ Max. range setting [K] [max]7.0 K
Diff. @ Max. range setting [K] [min]1.5 K
Diff. @ Max. range setting[°C] [max]7.0 °C
Diff. @ Max. range setting[°C] [min]1.5 °C
Diff. @ Min. range setting [K] [max]23.0 K
Diff. @ Min. range setting [K] [min]6.0 K
Diff. @ Min. range setting[°C] [max]23.0 °C
Diff. @ Min. range setting[°C] [min]6.0 °C
Differential typeAdjustable
EN 60947 electrical propertiesInsulation: 400VPollution degree: 3Rated impulse voltage: 4 kVShort circuit prot, fuse: 16A
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2Flex, no ferrules: 0.7-2.5 mm2Solid/stranded: 0.75-2.5 mm2
EU RoHS complianceYes
EU RoHS exemption clauseNo
Electrical connectionRubber cable gland
Electrical connection size6-14 mm
Characteristic
Value
Electrical spec. standardEN 60947-5
Enclosure rating IPIP30
Enclosure rating Nema (~)1
Material DescriptionKP62 Thermostat M/36
Max. sensor temperature [°C]120 °C
Max. sensor temperature [°F]248.0 °F
Other RoHS documentationSaudi Arabia RoHS
Packing formatMulti pack
Product TypeKP62
Product accessoriesSwitches accessories
Product descriptionThermostat
Product groupSwitches and thermostats
Product lineAir Conditioning and Commercial Refrigeration
Product nameThermostat
Quantity per packing format36 pc
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cadmium oxide (CAS no.1306-19-0)
Reset functionAuto
SCIP dossier no.be15a44e-80b1-41bd-9578-c8ff1cd7b9f3
Sensor size (Ø x L) [in]1 1/2 x 1 1/4 in
Sensor size (Ø x L) [mm]40 x 30 mm
Sensor typeRoom sensor
ServiceableNo
Temperature range [°C] [max]15 °C
Temperature range [°C] [min]-30 °C
Temperature range [°F] [max]59 °F
Temperature range [°F] [min]-22 °F
UL approval file nameE31024
UL evaluatedYes

General specifications

Characteristic
Value
Gross weight0.336 Kilogram
Net weight0.272 Kilogram
Volume0.57 Liter
Characteristic
Value
EAN/UPC5702428014533
Proposition 65Cancer and Reproductive Harm