Danfoss logo
OP-LPKM120LLP02E - OP-LPKM168LLP02E

Optyma™ Plus, OP-LPKM120LLP02E

114X3405

Segment usage: Low Back Pressure, Refrigerants: R404A; R452A; R454C; R448A; R455A; R449A, Compressor power supply [V]: 400/3/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]9200 m³/h
ApplicationsLBP
ApprovalCE
Capacity controlFixed speed
CE evaluatedYes
China RoHS complianceOut of scope
Compressor High pressure volume (L)0.50
Compressor Low pressure volume (L)5.95 L
Compressor modelLLZ024T4B
Compressor power supply [V]400/3/50
Condenser typeJ7
Condenser volume (L)1.97
Connection typeSolder
DescriptionOP-LPKM120LLP02E
DG Indicator ProfileNot relevant for dangerous goods
DLLP24
Electrical codeE
EU RoHS complianceOut of scope
FamilyOptyma™ Plus
Fan blade size [mm]560.000 mm
Fan cowl/grill typeH4
Fan current @ 50Hz [A]1.60 A
Fan diameter [mm]560 mm
Fan power consumption @ 50Hz [W]140 W
Fan power output @ 50Hz [W]72 W
Fan power supply [V/Ph/Hz]230/1/50
Filter Drier Volume (L)0.35
Frequency [Hz]50 Hz
High value of nominal voltage at 50Hz [V]415 V
In scope of WEEE and contain batteriesNo
Length [mm]650 mm
Liquid injectionYes
Characteristic
Value
Liquid line connection [in]3/4 in
Low value of nominal voltage at 50Hz [V]380 V
Material DescriptionOP-LPKM120LLP02E
Min fuse rating [A]25 A
Model numberOP-LPKM120LLP02E
No. of phases (compressor)3
No. of phases (fan)1
Number of fans2
Number of receivers2
Phase3
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
Product TypeOptyma™ Plus P02 (A2L)
REACH Candidate List substancesLead (CAS no. 7439-92-1)N,N-dimethylacetamide (CAS no. 127-19-5)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)Bisphenol A (BPA, CAS no. 80-05-7)
Receiver approvalCEMoroccoUKCA
Receiver typeVertical
Receiver volume [L]10.0 L
RefrigerantsR404AR448AR449AR452AR454CR455A
SCIP dossier no.8715baa0-315c-4422-97d8-0a8b45f1b46d
SCIP dossier product nameOPTYMA P02 G7 J7
Segment usageLow Back Pressure
Suction connection size [in]1-1/8 in
TechnologyScroll
Total height [mm]966.0 mm
UK RoHS complianceOut of scope
VersionP02
Voltage 50Hz [V]380 V
Voltage 50Hz [V] [Max]415 V
Volume (L)0.500 L
Width [mm]1835.00 mm

General specifications

Characteristic
Value
Gross weight230 Kilogram
Net weight180 Kilogram
Volume115.2 Liter
Characteristic
Value
EAN5702424596569
Proposition 65Cancer and Reproductive Harm