Danfoss logo
 OP-LPOM067LLP02E - OP-LPOM084LLP02E - OP-LPOM098LLP02E

Optyma™ Plus, OP-LPOM098LLP02E

114X3373

Segment usage: Low Back Pressure, Refrigerants: R404A; R452A; R448A; R449A, Compressor power supply [V]: 400/3/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]4300 m³/h
ApplicationsLBP
Capacity controlFixed speed
China RoHS complianceOut of scope
Compressor modelLLZ018T4A
Compressor power supply [V]400/3/50
Condenser Coil Internal Volume [L]1.62 mm³
Condenser typeG7
Connection typeSolder
Contain batteriesNo
CoolselectorFilterActive models
DG Indicator ProfileNot relevant for dangerous goods
DLLP24
DescriptionOP-LPOM098LLP02E
EU RoHS complianceOut of scope
Electrical codeE
FamilyOptyma™ Plus
Fan blade size [mm]500.000 mm
Fan cowl/grill typeGrill
Fan current @ 50Hz [A]0.96 A
Fan diameter [mm]500 mm
Fan power consumption @ 50Hz [W]190 W
Fan power output @ 50Hz [W]220 W
Fan power supply [V/Ph/Hz]230/1/50
Fan voltage @ 50Hz (max) [V] [Max]253 V
Fan voltage @ 50Hz (max) [V] [Min]207 V
Frequency [Hz]50 Hz
HMBP Cooling capacity range [kW] (R513A)Not available for this condition / refrigerant
High value of nominal voltage at 50Hz [V]440 V
In scope of WEEEYes
LBP Cooling capacity [kW] (R452A)3.87 kW
LBP Cooling capacity range [kW] (R452A)3.6 to 7.2 kW
LRA90 A
Length [mm]531 mm
Characteristic
Value
Liquid injectionYes
Liquid line connection [in]1/2 in
Low value of nominal voltage at 50Hz [V]360 V
MBP Cooling capacity range [kW] (R449A)Not available for this condition / refrigerant
MCC16 A
Material DescriptionOP-LPOM098LLP02E
Min fuse rating [A]20 A
Model numberOP-LPOM098LLP02E
No. of phases (compressor)3
No. of phases (fan)1
Number of fans1
Phase3
Product TypeOptyma™ Plus P02
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
REACH Candidate List substancesLead (CAS no. 7439-92-1)N,N-dimethylacetamide (CAS no. 127-19-5)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)Bisphenol A (BPA, CAS no. 80-05-7)
RLA10.2 A
Receiver approvalEACPEDRoHS
Receiver volume [L]6.2 L
RefrigerantsR404AR448AR449AR452A
SCIP dossier no.8715baa0-315c-4422-97d8-0a8b45f1b46d
SCIP dossier product nameOPTYMA P02 G7 J7
Segment usageLow Back Pressure
Sound power @ 50Hz [db(A)]74 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]63 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]43 dBA
Suction connection size [in]3/4 in
Total height [mm]965.0 mm
VersionP02
Voltage 50Hz [V]360 V
Voltage 50Hz [V] [Max]440 V
Width [mm]1441.00 mm

General specifications

Characteristic
Value
Gross weight168 Kilogram
Net weight136 Kilogram
Volume1032.3 Liter
Characteristic
Value
EAN/UPC5702428666329
Proposition 65Cancer and Reproductive Harm