Danfoss logo
 OP-LSVM026/34DSW05/W09G - OP-LSVM048/068NTW05/W09E/G - OP-MSIM034/044/046/057MLW05/W09E/G - OP-MSSM026/030CSW05/W09G - OP-MSTM021/022/026/034DSW05/W09E/G

Optyma™ Slim Pack, OP-MSIM046MLW05G

114X7271

Segment usage: Medium Back Pressure, Refrigerants: R404A; R452A; R407A; R134a; R454C; R407F; R513A; R448A; R455A; R449A, Compressor power supply [V]: 230/1/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]3300 m³/h
Air volume (EF002618)3300
ApplicationsMBP
ApprovalCE
Capacity ControlFixed speed
CE markYes
China RoHS complianceOut of scope
Compressor Low pressure volume (L)2.30 L
Compressor modelMLZ021T5
Compressor power supply [V]230/1/50
Condenser Coil Internal Volume [L]0.58 L
Condenser typeD7
Connection typeSolder
Connection voltage (EF003625)187
Contains batteriesNo
CoolselectorFilterActive models
Depth (EF000049)540
DescriptionOP-MSIM046MLW05G
DG Indicator ProfileNot relevant for dangerous goods
Electrical codeG
EU RoHS complianceOut of scope
FamilyOptyma™ Slim Pack
Fan blade size [mm]450.000 mm
Fan cowl/grill typeB2
Fan current @ 50Hz [A]0.47 A
Fan diameter [mm]450 mm
Fan power consumption @ 50Hz [W]110 W
Fan power output @ 50Hz [W]68 W
Fan power supply [V/Ph/Hz]230/1/50
Filter Drier Volume (L)0.17
Frequency [Hz]50 Hz
Height (EF000040)540
High value of nominal voltage at 60Hz [V]255 V
HMBP Cooling capacity [kW] (R513A/R134a)3.11 kW
HMBP Cooling capacity range [kW] (R513A/R134a)1.3 to 3.7 kW
In scope of WEEENo
LBP Cooling capacity range [kW] (R452A)Not available for this condition / refrigerant
Length [mm]464.0 mm
Liquid line connection [in]1/2 in
Low value of voltage range at 60Hz [V]187 V
Material DescriptionOP-MSIM046MLW05G
MBP Cooling capacity [kW] (R449A)4.88 kW
MBP Cooling capacity range [kW] (R22)Not available for this condition / refrigerant
MBP Cooling capacity range [kW] (R449A)3.7 to 8.3 kW
Characteristic
Value
MCC25 A
Min fuse rating [A]32 A
Model numberOP-MSIM046MLW05G
No. of phases (compressor)1
No. of phases (fan)1
Number of fans1
Number of phases (EF000351)1
Phase1
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
Product TypeOptyma™ Slim Pack W05 (A2L)
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)N,N-dimethylacetamide (CAS no. 127-19-5)
Receiver approvalCEEAC
Receiver typeVertical
Receiver volume [L]3.4 L
RefrigerantsR134aR404AR407AR407FR448AR449AR452AR454CR455AR513A
RLA16 A
SCIP dossier no.517dd61a-f0c7-4249-8639-17b34a9dfce2
SCIP dossier product nameOPTYMA W05
Segment usageMedium Back Pressure
Speed PlatformFixed-speed
Suction connection size [in]3/4 in
Suitable for type of refrigerant R134a (EF013569)TRUE
Suitable for type of refrigerant R22 (EF013579)FALSE
Suitable for type of refrigerant R290 (EF013580)FALSE
Suitable for type of refrigerant R32 (EF013567)FALSE
Suitable for type of refrigerant R401a (EF013581)FALSE
Suitable for type of refrigerant R402a (EF013582)FALSE
Suitable for type of refrigerant R404a (EF013568)TRUE
Suitable for type of refrigerant R407c (EF013583)FALSE
Suitable for type of refrigerant R413a (EF013584)FALSE
Suitable for type of refrigerant R417a (EF013585)FALSE
Suitable for type of refrigerant R507 (EF013570)FALSE
Total height [mm]690.0 mm
VersionW05
VersionDescriptionW05 : Optyma Slim Pack - Standard version
Voltage 50Hz [V]187 V
Voltage 50Hz [V] [Max]255 V
Volume (L)0.097 L
Weight (EF000167)85.00
Width (EF000008)540
Width [mm]1079.00 mm

General specifications

Characteristic
Value
Gross weight85 Kilogram
Net weight70 Kilogram
Volume552.636 Liter
Characteristic
Value
EAN/UPC5702424586263
Proposition 65Cancer and Reproductive Harm