Substations, DSA 1 MINI, Ilmenau, 10.2, 40.0 kW
146B5692
Ilmenau_10.2_1xH0: Insert Energy Meter, primary left/secondary right, High Temperature,without SV
Product specifications
Characteristic | Value |
---|---|
Allowed temperature [˚C] [Min] | 2 °C |
Application type | Indirect Heating |
Approval | CE |
Capacity [kW] | 40.0 kW |
Category name | Indirect heating substations |
CE evaluated | Yes |
Connection direction primary and secondary | left and right |
Contain batteries | No |
Cover material | EPP |
Current [A] [Max] | 2.0 A |
Delta P primary without heat meter [bar] [Min] | 0.38 bar |
Depth with cover [mm] | 482 mm |
Depth without cover [mm] | 482 mm |
Description | Ilmenau_10.2_1xH0: Insert Energy Meter, primary left/secondary right, High Temperature,without SV |
Design | Wall mounted |
DG Indicator Profile | Not relevant for dangerous goods |
DH connection size | 26,9x2,3mm |
DH connection type | welded |
DH pipe size | DN20 |
Differential pressure controller | AVQM |
Differential pressure primary [bar] [Max] | 20 bar |
Flow primary [m3/h] [Max] | 0.65 m³/h |
Flow secondary [m3/h] [Max] | 2.29 m³/h |
HE connection size | DN25 |
HE connection type | flange |
HE pipe size | DN25 |
Heating control type | Electronic |
Heating controller name | ECL310 |
Characteristic | Value |
---|---|
Heating HEX type | XB12L-1-20 |
Height with cover [mm] | 830 mm |
Height without cover [mm] | 830 mm |
HEX heating alloy | 1.4404 |
HEX heating brazed/gasketed material | Brazed copper |
Insulation material | EPP |
Manufacturer's name | danfoss |
Material Description | DSA1 MINI-DLR040-H0__IL |
Number of heating manifold connections [loops] [Max] | 1 |
Package depth [mm] | 800 mm |
Package height [mm] | 620 mm |
Package width [mm] | 1200 mm |
PED category | § 4.3 |
Pressure nominal primary [bar] | 25 bar |
Pressure nominal secondary [bar] | 6 bar |
Pressure primary [bar] [Max] | 25 bar |
Pressure secondary [bar] [Max] | 3 bar |
Product group | Substations |
Product line | Heavy Duty Stations |
Product Type | DSA 1 MINI |
REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
Sensor type heatmeter | direct |
Substation version | Ilmenau, 10.2 |
Supply temperature construction [˚C] | 130 °C |
Supply voltage [V] AC | 230 V |
Width with cover [mm] | 880 mm |
Width without cover [mm] | 880 mm |
General specifications
Characteristic | Value |
---|---|
Gross weight | 70 Kilogram |
Net weight | 50 Kilogram |
Characteristic | Value |
---|---|
EAN | 5715162740262 |
Proposition 65 | Cancer and Reproductive Harm |