Substations, DSP MOD, Heating controller name: ECL310
200B0018
DSP1-MOD@-IB065-080-0000-ML-FR-PN25-0667, 667 kW, ECL310, Lacroix Sofrel, Distech, 25bar, 110°C
Product specifications
Characteristic | Value |
---|---|
Allowed temperature [˚C] [Min] | 2 °C |
Application type | Indirect Heating |
Approval | CE |
Approval standard | CE |
Category name | Indirect heating substations |
CE evaluated | Yes |
Cover material | Without |
Cover option | No |
Depth without cover [mm] | 1010 mm |
Description | DSP1-MOD@-IB065-080-0000-ML-FR-PN25-0667, 667 kW, ECL310, Lacroix Sofrel, Distech, 25bar, 110°C |
Design | standing |
DG Indicator Profile | Not relevant for dangerous goods |
DH connection size | DN65 |
DH connection type | flange |
DH pipe size | DN65 |
Differential pressure primary [bar] [Max] | 16 bar |
Flow primary [m3/h] [Max] | 19.40 m³/h |
Flow secondary [m3/h] [Max] | 29.10 m³/h |
HE connection size | DN80 |
HE connection type | flange |
Characteristic | Value |
---|---|
HE pipe size | DN80 |
Heating control type | Electronic |
Heating controller name | ECL310 |
Height without cover [mm] | 1640 mm |
HEX heating alloy | 1.4404 |
HEX heating brazed/gasketed material | Gasketed EPDM |
Insulation material | PU Hard Foam |
Manufacturer's name | danfoss |
Material Description | DSP1-MOD@-IB065-080-0000-ML-FR-PN25-0667 |
Pressure nominal primary [bar] | 25 bar |
Pressure nominal secondary [bar] | 16 bar |
Pressure primary [bar] [Max] | 25 bar |
Pressure secondary [bar] [Max] | 16 bar |
Product group | Substations |
Product line | Heavy Duty Stations |
Product Type | DSP MOD |
Sensor type heatmeter | pocket 6mm |
Supply temperature construction [˚C] | 110 °C |
Supply voltage [V] AC | 230 V |
Width without cover [mm] | 2929 mm |