Danfoss logo
RA-N DN 15 Straight S Back

Radiator Valves, RA-N PURE, Normal flow, DN 15, S

015G0074

Normal flow valves with presetting

Product specifications

Characteristic
Value
Application2-pipe system
CE evaluatedOut of scope
Connection size inRp 1/2
Connection size outM26 x 1,5
Connection typesInternal thread
Contain batteriesNo
DG Indicator ProfileNot relevant for dangerous goods
DescriptionNormal flow valves with presetting
DesignStraight
Differential pressure range [bar] [Max]0.60 bar
Dimension standardS
FinishNickel plated
Flow temperature [°C] [Max]120 °C
Kv value at setting 1 [m³/h]0.040 m³/h
Kv value at setting 2 [m³/h]0.090 m³/h
Kv value at setting 3 [m³/h]0.160 m³/h
Kv value at setting 4 [m³/h]0.250 m³/h
Characteristic
Value
Kv value at setting 5 [m³/h]0.360 m³/h
Kv value at setting 6 [m³/h]0.430 m³/h
Kv value at setting 7 [m³/h]0.520 m³/h
Kv value at setting N [m³/h]0.730 m³/h
Kvs values [m³/h]0.90 m³/h
Material DescriptionRA-N PURE 15 S "S"
Presettingyes
Product TypeRA-N PURE
Product groupRadiator Valves
Product lineMechanical TRV
Tailpiece typeMetric thread
Test pressure [bar]16 bar
UL evaluatedOut of scope
Valve sizeDN 15
Valve typeNormal flow
Working pressure [bar] [Max]10 bar

General specifications

Characteristic
Value
Gross weight0.182 Kilogram
Net weight0.172 Kilogram
Characteristic
Value
EAN/UPC5715162425756