Check Valve, NVD 812, PN 40, DN 15, Between Flange
065B7530
NVD 812 PN40 DN15
Product specifications
Characteristic | Value |
---|---|
Application | District Heating |
China RoHS compliance | Out of scope |
Connection types | Between Flange |
Description | NVD 812 PN40 DN15 |
DG Indicator Profile | Not relevant for dangerous goods |
Diameter [mm] | 15 mm |
EU RoHS compliance | Out of scope |
Function | Non-return |
In scope of WEEE and contain batteries | No |
Kvs values [m³/h] | 4.24 m³/h |
Label product | Yes |
Material Description | NVD 812 PN40 DN15 |
Media pH [Max] | 10 |
Media pH [Min] | 7 |
Media temperature [°C] [Max] | 350 °C |
Media temperature [°C] [Min] | -10 °C |
Characteristic | Value |
---|---|
Medium alternative | Glycolic water up to 50% |
Medium alternative 2 | Domestic water |
Mounting orientation | free |
Number of ports | 2 |
Operation type | Self-operating |
Permissible media | District heating/cooling circulation water |
Pressure class | PN 40 |
Pressure nominal [bar] | 40 bar |
Product group | Butterfly valves |
Product line | District Energy Controls |
Product Type | NVD 812 |
REACH Candidate List substances | No |
UK RoHS compliance | Out of scope |
Valve body material | Stainless steel |
Valve size | DN 15 |
Valve type | Check Valve |
General specifications
Characteristic | Value |
---|---|
Gross weight | 0.08 Kilogram |
Net weight | 0.07 Kilogram |
Volume | 0.06 Liter |
Characteristic | Value |
---|---|
EAN | 5710104063546 |
Proposition 65 | No Reproductive Toxins or Carcinogens |