Danfoss logo

The Danfoss electrical actuators for combination with our control vales provide a new level of convenience through excellent control performance and quality features. The actuators provide risk reduction trough improved overload protection, which ensures trouble-free operation of the actuator inside the system.

The motorized control valves ensure stable and accurate control of water. This in turn improves temperature control, leading to enhanced comfort for the end-user. Good control ratios and rapid response times to changes in domestic hot water supply requirements are just some of the features needed to ensure optimum control performance.

Product Highlights
  • Easy selection, installation, commissioning and maintenance mean less time, money and effort
  • Built-in thermic and overload protection of the electromotor
  • External LED visualization and signaling save time and effort during installation and commissioning of MCVs
Actuator features:
  • Anti-oscillation
  • Control ratio
  • Stroke limitation
  • Split characteristics
  • Modification of controls characteristic (65X actuators)

Product types shown: 25

  • Tile image

    ABV

    • 24 V or 230/240 V
    • Direct-acting or reverse-acting versions
    • Power consumption 9 VA
    • Built-in manual operation
    • Built-in kv limiting
    • For type RAV, VMA and VMT 2-way valves
    • For type VMV and KOVM 3-way valves

  • Tile image

    AME 10/20/30, AME 13/23/33

    Actuators with safety function (AME 13, AME 23 or AME 33) and actuators without safety function (AME 10, AME 20 or AME 30) are mainly used with VS, VM, VB, AVQM and VMV (only with AME 10) valves. Safety version is activated automatically in case of power failure or if the power supply is switched off by the safety thermostat. Actuators automatically adapt stroke to valve end positions which reduces commissioning time.

  • AME 130(H) / AME 140(H) category image

    AME 130(H) / AME 140(H)

    AME 130, AME 140, AME 130H and AME 140H actuators are used with:

    • VZ DN 15, 20,
    • VZL DN 15, 20 with stem extension plug or
    • AHQM (DN 15-32) valves.

    The actuator can be used with fan coil units, induction units, small reheaters, recoolers, and zone applications in which hot/cold water is the controlled medium.

  • AME 13SU / AME 23SU category image

    AME 13SU / AME 23SU

    The actuators with safety function are mainly used with VZ valve (AME 13SU) or with VS, VM and VB valves (AME 13SU, AME 23SU) or AVQM ( AME 23 SU). Safety version is activated automatically in case of power failure or if the power supply is switched off by the safety thermostat.

  • AME 25 / AME 35 category image

    AME 25 / AME 35

    AME electric actuators are used with, VRB, VRG, VF, VL valves with additional adapter (Code No. 065Z0311, not supplied) and VFS 2 valves up to DN 50 diameter.

    ​​​​​​​The actuator automatically adapts its stroke to valve end positions which reduces commissioning time.

  • AME 25 SD / AME 25 SU category image

    AME 25 SD / AME 25 SU

    AME 25 SD or SU electric actuators are used with valves gen.2009 type VRB, VRG, VF, VL with additional adapter (Code No. 065Z0311, not supplied) and VFS 2 valves up to DN 50 diameter. The actuator automatically adapts itsstroke to valve end positions which reducescommissioning time.

  • AME 438 SU category image

    AME 438 SU

    AME 438 SU actuator is used with two and three-way valves type VRB, VRG, VF and VL up to DN 50 diameter.

  • AME 55 / AME 56 category image

    AME 55 / AME 56

    The actuators AME 55 / AME 56 are used with valves: VFM 2 (DN 65-150) only in combination with AME 55, VFS 2 (DN 15-50) only in combination with AME 56. Clutch available on special request, VFS 2 (DN 65-100), VL 2/3 (DN 100), VF 2/3 (DN 100-150), VL 2/3 & VF 2/3 (DN 65, 80)-only in combination with AME 56 and adapter 065Z0312, AFQM (DN 65-125) and AFQM 6 (DN 40-50).

  • Tile image

    AME 655(GA)/ 658 SU / 658 SD/ 659 SD

    Actuators are primarily designed to regulate valve in the respond to the demand of a controller in District Heating/cooling, Heating, Ventilating and Air conditioning systems. Actuators AME 655, 658 and 659 can be controlled by electronic controllers with modulating or 3-point control output. Actuators can be used without any adapter in combination with: - Valve types VFM, VFS (DN 65-100), VF (DN 100-150) and VL (DN 100) - Self-acting flow controller AFQM 6* and AFQM 2. * With adapter 065B3527 for AFQM 6 or AFQM PN 25, if produced before March 2015. Used with adapter 065B3527 in combination with: - Valve types VFG(S) and VFU.

  • AME 685 category image

    AME 685

    The actuator is designed to control the valve in response to the demand of a controller in District Heating/cooling, Heating, Ventilating and Air conditioning systems.

    The AME 685 can be controlled by electronic controllers with modulating or 3-point control output.
    ​​​​​​​
    ​​​​​​​The actuator can be used in combination with valve type VF 3 (DN 200-300).

  • AME 85 / AME 86 category image

    AME 85 / AME 86

    The actuators AME 85 and AME 86 are used with VFM 2 (DN 150-250), VFS 2 (DN 65-100), VF2/3 (DN 125, 150) and AFQM (DN150-250) valves.

  • AME 855 category image

    AME 855

    Actuator is primarily designed to regulate valve in the respond to the demand of a controller in District Heating/cooling, Heating, Ventilation and Air conditioning systems. Actuator AME 855 can be controlled by electronic controllers with modulating or 3-point control output. Actuator can be used with VF3 valves (DN 200-300).

  • AMV 10/20/30/ AMV 13/23/33 category image

    AMV 10/20/30/ AMV 13/23/33

    Actuators with safety function (AMV 13, AMV 23 or AMV 33) and actuators without safety function (AMV 10, AMV 20 or AMV 30) are mainly used with VS, VM, VB, AVQM and VMV (only with AMV 10) valves.
    Safety version is activated automatically in case of power failure or if the power supply is switched off by the safety thermostat. Actuators automatically adapt stroke to valve end positions which reduces commissioning time.

    Main data:

    • Nominal voltage:
      - 24 Vac, 50 Hz/60 Hz
      - 230 Vac, 50 Hz/60 Hz
    • Control input signal: 3 point
    • Force:
      - AMV 10, 13 ...............................300 N
      - AMV 20, 23, 30, 33 .................. 450 N
    • Speed:
      - AMV 10, 13 ......................... 14 s/mm
      - AMV 20, 23 ......................... 15 s/mm
      - AMV 30, 33 ............................3 s/mm
    • Max. medium temperature:
      - AMV 10, 13 .............130 °C (150 °C*)
      - AMV 20, 23, 30, 33 ................. 150 °C
    • End-position signals
    * with High temperature adapter (065Z7547)

  • AMV 13 SU / AMV 23 SU category image

    AMV 13 SU / AMV 23 SU

    The actuators with safety function are mainly used with VZ valves (AMV 13 SU) or with VS, VM or VB valves (AMV 13 SU, AMV 23 SU) or AVQM (AMV 23 SU). Safety version is activated automatically in case of power failure or if the power supply is switched off by the safety thermostat. The actuator automatically adapts its stroke to valve end positions which reduces commissioning time. Optional feedback potentiometer is available on special request.

  • AMV 130(H) / AMV 140(H) category image

    AMV 130(H) / AMV 140(H)

    AMV 130/140 and AMV 130H/140H actuators are used with:
    - VZ DN 15, 20,
    - VZL DN 15, 20 with stem extension plug or
    - AHQM (DN 15-32) valves.

    The actuator can be used with fan coil units, induction units, small reheaters, recoolers and zone applications in which hot/cold water is the controlled medium.

  • AMV 150 category image

    AMV 150

    Actuator is primarily designed to regulate valve in the respond to the demand of a controller in District heating, heating, floor heating, solar heating, zone heating, comfort cooling, ventilating and air conditioning systems etc.

    Actuator should be controlled by electronic controllers with triacs or solid state relays with zero cross detection.

    Actuator can be used in combination with:
    - Valve types VS 2 (DN 15 only) and VMV
    - Self acting flow controller AVQM (DN15 only)
    ​​​​​​​
    Note: If a controller with relay outputs is used then relays with higher current rating and inrush current capabilities (min. 40A) should be selected.

  • AMV 20 SL / AMV 23 SL / AMV 30 SL category image

    AMV 20 SL / AMV 23 SL / AMV 30 SL

    The actuators for 3-point controls with or without safety function are suitable to be used with VS2, VM2, VB2 and AVQM valves. The safety function on AMV 23 SL is activated automatically in case of power failure or if the power supply is switched off by the safety thermostat. This function provides safety shut off on power failure. In addition to basic function such as manual control and position indication, the actuators are also equipped with force sensitive switch-off to ensure that actuators and valves are not exposed to overload. This function automatically ensures the self-adjustment of the end positions on the valve. Actuators are also equipped with stroke limitation that can limit flow in valves. Limitation of stroke is designed with switch that can be set in any desirable position (stroke limit from 0 to 100%).

  • AMV 25 / AMV 35 category image

    AMV 25 / AMV 35

    AMV electric actuators are used with, VRB, VRG, VF, VL valves with additional adapter (Code No. 065Z0311, not supplied) and VFS 2 valves up to DN 50 diameter.

    The actuator automatically adapts its stroke to valve end positions which reduces commissioning time. Optional auxiliary switches, feedback potentiometer and valve stem heater are available.

  • AMV 25 SD / AMV 25 SU category image

    AMV 25 SD / AMV 25 SU

    AMV 25 SD or SU electric actuators are used with valves gen.2009 type VRB, VRG, VF, VL with additional adapter (Code No. 065Z0311, not supplied) and VFS 2 valves up to DN 50 diameter. The actuator automatically adapts its stroke to valve end positions which reduces commissioning time. Optional auxiliary switches, feedback potentiometer and valve stem heater are available.

  • AMV 435 category image

    AMV 435

    AMV 435 series of actuator is used with 2-way pressure independent control valve type AB-QM in sizes ranging 1½ to 4”.

  • AMV 438 SU category image

    AMV 438 SU

    AMV 438 SU actuator is used with two and three-way valves type VRB, VRG, VF and VL up to DN 50 diameter.

  • AMV 55 / AMV 56 category image

    AMV 55 / AMV 56

    The actuators are used with valves:

    • VFM2 (DN 65-150) only in combination with AMV 55,
    • VFS 2 (DN 15-50) only in combination with AMV 56 and clutch 065Z7551,
    • VFS 2 (DN 65-100),
    • VL 2/3 (DN 100),
    • VF 2/3 (DN 100-150),
    • VL 2/3 & VF 2/3 (DN 65, 80) only in combination with AMV 56 and adapter 065Z0312,
    • or AFQM (DN 65-125) and AFQM 6 (DN 40-50)

  • AMV 655 / 658 SU / 658 SD category image

    AMV 655 / 658 SU / 658 SD

    Actuators are primarily designed to control the valve in response to the demand of a controller in District Heating/cooling, Heating, Ventilating and Air conditioning systems. Actuators AMV 655 and 658 can be controlled by electronic controllers with 3-point output. Ordering Actuators can be used without any adapter in combination with: - Valve types VFM, VFS (DN 65-100), VF (DN 100-150) and VL (DN 100) - Self-acting flow controller AFQM 6 and AFQM*. * With adapter 065B3527 for AFQM 6 or AFQM PN 25, if produced before March 2015. Used with adapter 065B3527 in combination with: - Valve types VFG(S) and VFU.

  • AMV 85 / AMV 86 category image

    AMV 85 / AMV 86

    The actuators AMV 85 and AMV 86 are used with VFM 2 (DN 150-250), VFS 2 (DN 65-100), VF2/3 (DN 125, 150) and AFQM (DN150-250) valves.

  • TWA-ZL category image

    TWA-ZL

    Danfoss thermal actuator TWA-ZL is used with Danfoss valves type VZL. The actuator can be controlled with a on/off controller or switch. The actuator can be controlled with an on/off controller, pulse width modulation (PWM) or switch.

    These provide a cost effective solution for the control of hot and/or chilled water for fan coil units, small reheaters and recoolers in temperature control systems.

    Main data:

    • Nominal voltage: 24 V AC/DC or 230 V AC ; 50/60 Hz
    • Stroke: 2,8 mm
    • Full stroke travel time: 3 min
    • Max. medium temperature: 120 °C