Danfoss logo
SonoSelect_Safe left angle perspective

Energy meters, SonoSafe 10, 25 mm, qp [m³/h]: 3.5, Heating, Battery 1 A-cell, No integrated communication, Radio OMS 868.95 MHz

014U0245

Energy meter for residential applications

Product specifications

Characteristic
Value
1 Primary battery SUM weight Kg0.018
1 Primary battery weight Kg0.018
2 Secondary battery SUM weight Kg0.010
2 Secondary battery weight Kg0.010
Accuracy standardClass 2 to EN1434
Ambient classE1 / M2
Ambient humidity [% RH] [Max]95 %
Ambient temperature [°C] [max]55 °C
Ambient temperature [°C] [min]5 °C
ApplicationHeating
Approval authorityForce Certification
Approved meteorological range [°C] [Max]95 °C
Approved meteorological range [°C] [Min]5 °C
Battery lifetime [Years]16 yr
Battery qty1
Battery type or NameAA Lithium
Cable insulation materialPVC halogen free
Cable length between calculator and flow sensor [m]0.5 m
China RoHS complianceOut of scope
Commissioning toolSonoApp
Connection sizeG 1 1/4 B
Connection typesThread
DescriptionEnergy meter for residential applications
DG Indicator ProfileContains Lithium Batteries
Diameter [mm]25 mm
Difference temperature limits (Accounting) [K] [Max]90.00 K
Difference temperature limits (Accounting) [K] [Min]3.00 K
Display typeLCD
Dynamic range1:100
EEE category5 small equipment (any external dimension < 50 cm)
Energy unitkWh (without digit after comma)
EU RoHS complianceOut of scope
Flow measuring principleUltrasonic
Housing colorRAL 9010 White
In scope of WEEEYes
In scope of WEEE and contain batteriesYes
InstallationReturn
Integrated communicationNo integrated communication
Interface module slot 1Radio OMS 868.95 MHz
Characteristic
Value
IP protection classIP65
Kvs values [m³/h]9.71 m³/h
Length [mm]260 mm
Log storage duration [Month]24 mo
Log storage interval [Month]1 mo
Material DescriptionDN25R,qp3.5,260,L,EU,kWh,Radio+PI
Material in contact with mediumBrass sensor
MediaHeating system according to VDI 2035
Media temperature [°C] [Max]95 °C
Media temperature [°C] [Min]5 °C
Pressure nominal [bar]16 bar
Product groupEnergy meters
Product lineDistrict Energy Controls
Product TypeSonoSafe 10
Protection class calculatorIP65
qc [m³/h]0.0070 m³/h
qi [m³/h]0.035 m³/h
qp [m³/h]3.5 m³/h
qs [m³/h]7.0 m³/h
qss [m³/h]7.70 m³/h
REACH Candidate List substancesLead (CAS no. 7439-92-1)
SCIP dossier no.c284e070-c802-4ced-837c-2aa2fcd3510f
SCIP dossier product nameUltrasonic Pathfinder
Secondary battery Number of batteries1
Secondary battery Type or name0,5 AA Lithium
Secondary battery Voltage3.6 V
Secondary battery Weight per battery10 g
Storage temperature [°C] [Max]60 °C
Storage temperature [°C] [Min]-25 °C
Supply voltage [V] DC4 V
Supply voltage typeBattery 1 A-cell
Temperature sensor approved temperature [°C] [Max]105 °C
Temperature sensor approved temperature [°C] [Min]0 °C
Temperature sensor diameter [mm]5.2 mm
Temperature sensors cable length [m]1.5 m
Temperature sensors typePt 1000
UK RoHS complianceOut of scope
Weight per battery18 g

General specifications

Characteristic
Value
Gross weight1.751 Kilogram
Net weight1.751 Kilogram
Volume6.344 Liter
Characteristic
Value
EAN5702425150678
Proposition 65Cancer and Reproductive Harm