Product specifications

Characteristic
Value
1 Primary battery SUM weight Kg0.038
1 Primary battery weight Kg0.019
Accuracy standardClass 2 to EN1434
Ambient classE2/M1
Ambient humidity [% RH] [Max]93 %
Ambient temperature [°C] [max]55 °C
Ambient temperature [°C] [min]5 °C
ApplicationHeating
Approval authorityMID
Approved meteorological range [°C] [Max]180 °C
Approved meteorological range [°C] [Min]0 °C
Battery lifetime [Years]11 yr
Battery qty2
Battery type or NameAA Lithium (ER14505)
Cable length between calculator and flow sensor [m]5.0 m
China RoHS complianceOut of scope
Connection typesFlange
Contain batteriesYes
DG Indicator ProfileContains Lithium Batteries
DescriptionEnergy meter for commercial applications
Display typeLCD
Dynamic range1:100
EEE category5 small equipment (any external dimension < 50 cm)
EU RoHS complianceOut of scope
Energy unitkWh
Flow measuring principleUltrasonic
Characteristic
Value
In scope of WEEEYes
InstallationReturn
Integrated communication2 Pulse inputs/outputs
Interface module slot 1M-bus module
Kvs values [m³/h]43.30 m³/h
Log storage duration [Month]36 mo
Material DescriptionSONO30 DN50 qp15 270 fl R HE 3.6V M-Bus
Media temperature [°C] [Max]130 °C
Media temperature [°C] [Min]5 °C
Media temporary overload temperature [°C]150 °C
Pressure nominal [bar]25 bar
Product TypeSonoMeter 30
Product groupEnergy meters
Product lineDistrict Energy Controls
REACH Candidate List substancesLead (CAS no. 7439-92-1)
SCIP dossier no.f1245927-0732-4fe6-8dbd-60859e22c197
SCIP dossier product nameSonometer 30 DN15-100
Storage temperature [°C] [Max]60 °C
Storage temperature [°C] [Min]-25 °C
Supply voltage typebattery 2 x AA-cell
Temperature sensor diameter [mm]5.2 mm
Temperature sensors cable length [m]5.0 m
Temperature sensors typePt 500
Weight per battery19 g
qp [m³/h]15.0 m³/h

General specifications

Characteristic
Value
Gross weight6.953 Kilogram
Net weight6.4 Kilogram
Volume8.789 Liter
Characteristic
Value
EAN/UPC5702428532341
Proposition 65Cancer and Reproductive Harm