ECL Comfort 310, LCD dot matrix, Supply voltage [V] AC: 207 - 244
087H3050
ECL COMFORT 310B/230 V
Product specifications
Characteristic | Value |
---|---|
Actuator output load [VA] | 15.000 VA |
Ambient humidity [% RH] [Max] | 65 % |
Ambient temperature [°C] [max] | 55 °C |
Ambient temperature [°C] [min] | 0 °C |
Application source | By ECL application key |
Approval | CE |
Approval standard | EMC-Directive: 2004/108/ECEmission: EN 61000-6-3:2007EN 60730Immunity: EN 61000-6-1:2007LVD directive 2006/95/EC |
Basic Data Text Template | Heizungsregler ECL Comfort 310B<br>Zentralgerät zur witterungsgeführten<br>Vorlauftemperaturregelung mit oder ohne<br>Brauchwasserbereitung für direkt oder<br>indirekt angeschlossene Nah- und Fern-<br>wärmeanlagen, für Kessel- oder<br>Lüftungsanlagen,<br>Ohne Display und ohne Bedienelement,<br>eine Fernbedieneinheit ECA30 oder ECA31<br>ist zur Einstellung notwendig (nicht im<br> Lieferumfang enthalten).<br>Softwarevorgabe über intelligente<br>Applikations-Karte, inklusive gleitender<br>Rücklauftemperaturbegrenzung,<br>Frostschutzfunktion, min.- und max.<br>Vorlauftemperatur-Begrenzung,<br>Sommerausschaltung, Nachtabsenkung,<br>einstellbarer Heizkennlinie und<br>Parallelverschiebung, Regelung der<br>Raumtemperatur, Fühlerüberwachung,<br>Stellantriebsschutz und<br>Pumpenintervallschaltung, Sommer-<br>Winterzeitumschaltung,<br>- Datenbus RS485 (intern) für<br>Fernbedienungs-<br> einheiten, Zusatzmodule oder den<br>Einsatz als<br> Master oder Slave in einer Master-<br>Slave-Folge-<br> regelung.<br>- Mod-Bus-Schnittstelle für Vernetzung<br>und<br> Datenfernauslesung<br>- M-Bus-TCP-Schnittstelle<br>6 Fühlereingänge PT1000,<br> Impulseingang<br>4 frei konfig. Eingänge 0-10V oder<br>PT1000<br>1 USB-Service-Schnittstelle,<br>3 Paar Triacausgänge<br>6 Relaisausgänge,<br>1 USB-Service-Schnittstelle,<br>Für Wandmontage oder Einbau in<br>Schaltschrank auf DIN-Schiene<br>(Sockel dazu als Zubehör erhältlich)<br>Bedienung nur über Fernbedien-<br>einheit ECA30 oder ECA31 möglich<br>(als Zubehör erhältlich)<br>Versorgungsspannung: 230V, AC<br>Leistungsaufnahme: 5 VA<br>Schutzart: IP 41<br>Gehäuseabmessung: 220 x 110<br>Fabrikat: Danfoss<br>Typ: ECL Comfort 310<br>Bestell-Nr.: 087H3050 |
CE evaluated | Yes |
China RoHS compliance | Out of scope |
Communications | ECL 485 Bus (non-galvanically isolated)M-BusModbus (galvanically isolated) |
Contain batteries | No |
DG Indicator Profile | Not relevant for dangerous goods |
DHW functions | Anti-bacteria programAuto-tunningReturn temperature influence |
Description | ECL COMFORT 310B/230 V |
Digital inputs type | 12 V pull-up possible |
Display type | LCD dot matrix |
EEE category | 5 small equipment (any external dimension < 50 cm) |
EU RoHS compliance | Yes with exemptions |
EU RoHS exemption clause | 6(c) |
General functions | Alarm functionsCirculation pump exerciseControl valve exerciseExternal override facilityFrost protectionHoliday programMaster - Slave networkMotor protectionRemote control connection |
Grade of enclosure | IP41 |
Heat curve setting for heating circuit | 6 pointsSlope |
In scope of WEEE | Yes |
Material Description | ECL COMFORT 310B/230 V |
Number of 3-point motor control outputs | 3 |
Number of DHW circuits | 2 |
Number of DHW storage tank circuits | 1 |
Characteristic | Value |
---|---|
Number of Sensor inputs | 10 pc |
Number of comfort periods per day | 3 |
Number of digital inputs | 4 |
Number of heating circuits | 3 |
Number of pumps | 5 |
Number of relay outputs | 6 |
Power consumption [W] | 5.0 W |
Product Type | ECL Comfort 310 |
Product group | Electronic controllers |
Product line | District Energy Controls |
REACH Candidate List substances | Lead (CAS no. 7439-92-1)Lead monoxide (PbO, CAS no. 1317-36-8)Diboron trioxide (B2O3, CAS no. 1303-86-2)Lead titanium trioxide (CAS no. 12060-00-3)6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol (CAS no. 119-47-1) |
Relay output inductive load [A] | 2 A |
Relay output ohmic load [A] | 4 A |
Relay output voltage [V] AC | 230 V |
SCIP dossier no. | ad51fccb-924b-4843-a9b7-7e3da2fef171 |
SCIP dossier product name | ECL Comfort 310 and 210 |
Sensor cable length [m] | 200.00 m |
Sensor cable length [mm] | 200 mm |
Storage temperature [°C] [Max] | 70 °C |
Storage temperature [°C] [Min] | -40 °C |
Supply voltage [V] AC | 230 V |
Supply voltage [V] AC [max] | 244 V |
Supply voltage [V] AC [min] | 207 V |
Supply voltage frequency [Hz] | 50 Hz |
Temperature sensors type | Pt 1000, configurable input |
Time switch power backup [h] | 72 h |
Time switch type | Week |
General specifications
Characteristic | Value |
---|---|
Gross weight | 0.618 Kilogram |
Net weight | 0.433 Kilogram |
Volume | 4.859 Liter |
Characteristic | Value |
---|---|
EAN/UPC | 5710104013268 |
Proposition 65 | Cancer and Reproductive Harm |