ECL Comfort 310, LCD dot matrix, Supply voltage [V] AC: 207 - 244
087H3040
ECL COMFORT 310/230 V
Product specifications
Characteristic | Value |
---|---|
Actuator output load [VA] | 15.000 VA |
Ambient humidity [% RH] [Max] | 65 % |
Ambient temperature [°C] [max] | 55 °C |
Ambient temperature [°C] [min] | 0 °C |
Application source | By ECL application key |
Approval | CE |
Approval standard | EMC-Directive: 2004/108/ECEmission: EN 61000-6-3:2007EN 60730Immunity: EN 61000-6-1:2007LVD directive 2006/95/EC |
CE evaluated | Yes |
China RoHS compliance | Out of scope |
Communications | ECL 485 Bus (non-galvanically isolated)M-BusModbus (galvanically isolated) |
Description | ECL COMFORT 310/230 V |
DG Indicator Profile | Not relevant for dangerous goods |
DHW functions | Anti-bacteria programAuto-tunningReturn temperature influence |
Digital inputs type | 12 V pull-up possible |
Display type | LCD dot matrix |
EEE category | 5 small equipment (any external dimension < 50 cm) |
EU RoHS compliance | Yes with exemptions |
EU RoHS exemption clause | 6(c) |
General functions | Alarm functionsCirculation pump exerciseControl valve exerciseExternal override facilityFrost protectionHoliday programMaster - Slave networkMotor protectionRemote control connectionVisible temperature logging |
Grade of enclosure | IP41 |
Heat curve setting for heating circuit | 6 pointsSlope |
In scope of WEEE | Yes |
In scope of WEEE and contain batteries | No |
Material Description | ECL COMFORT 310/230 V |
Number of 3-point motor control outputs | 3 |
Number of comfort periods per day | 3 |
Number of DHW circuits | 2 |
Number of DHW storage tank circuits | 1 |
Number of digital inputs | 4 |
Characteristic | Value |
---|---|
Number of heating circuits | 3 |
Number of pumps | 5 |
Number of relay outputs | 6 |
Number of Sensor inputs | 10 pc |
Power consumption [W] | 5.0 W |
Product group | Electronic controllers |
Product line | District Energy Controls |
Product Type | ECL Comfort 310 |
REACH Candidate List substances | Lead (CAS no. 7439-92-1)Lead monoxide (PbO, CAS no. 1317-36-8)Diboron trioxide (B2O3, CAS no. 1303-86-2)Lead titanium trioxide (CAS no. 12060-00-3)6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol (CAS no. 119-47-1) |
Relay output inductive load [A] | 2 A |
Relay output ohmic load [A] | 4 A |
Relay output voltage [V] AC | 230 V |
SCIP dossier no. | ad51fccb-924b-4843-a9b7-7e3da2fef171 |
SCIP dossier product name | ECL Comfort 310 and 210 |
Sensor cable length [m] | 200.00 m |
Storage temperature [°C] [Max] | 70 °C |
Storage temperature [°C] [Min] | -40 °C |
Supply voltage [V] AC | 230 V |
Supply voltage [V] AC [max] | 244 V |
Supply voltage [V] AC [min] | 207 V |
Supply voltage frequency [Hz] | 50 Hz |
Temperature sensors type | Pt 1000, configurable input |
Time switch power backup [h] | 72 h |
Time switch type | Week |
UK RoHS compliance | Out of scope |
User input type | DisplayPush-turn dial |
VVS Number DK | 460944310 |
VVS Number FI | 4364753 |
VVS Number SE | 5384302 |
General specifications
Characteristic | Value |
---|---|
Gross weight | 0.682 Kilogram |
Net weight | 0.476 Kilogram |
Volume | 4.877 Liter |
Characteristic | Value |
---|---|
EAN | 5710104013244 |
Proposition 65 | Cancer and Reproductive Harm |