Danfoss logo
ECL120_100B1200_R

ECL Comfort 120, Supply voltage [V] AC: 207 - 244, Time switch type: Week

100B1603

ECL Comfort 120, I-pack

Product specifications

Characteristic
Value
Actuator output load [VA]15.000 VA
Ambient humidity [% RH] [Max]95 %
Ambient temperature [°C] [max]55 °C
Ambient temperature [°C] [min]-5 °C
Application sourceOn-board
ApprovalCEEACUKCAUA
CE evaluatedYes
CommunicationsModbus (galvanically isolated)
Contain batteriesNo
DG Indicator ProfileNot relevant for dangerous goods
DescriptionECL Comfort 120, I-pack
EU RoHS complianceYes with exemptions
General functionsAlarm functionsCirculation pump exerciseControl valve exerciseExternal override facilityFrost protectionMaster - Slave networkRemote control connection
Grade of enclosureIP41
Heat curve setting for heating circuit6 pointsSlope
Material DescriptionECL Comfort 120, I-pack (24 pcs)
Number of 3-point motor control outputs1
Number of Sensor inputs4 pc
Number of comfort periods per day3
Number of digital inputs1
Number of heating circuits1
Characteristic
Value
Number of pumps1
Number of relay outputs1
Power consumption [W]3.0 W
Product TypeECL Comfort 120
Product groupElectronic controllers
Product lineDistrict Energy Controls
REACH Candidate List substancesLead (CAS no. 7439-92-1)Lead monoxide (PbO, CAS no. 1317-36-8)Diboron trioxide (B2O3, CAS no. 1303-86-2)Lead titanium trioxide (CAS no. 12060-00-3)Disodium octaborate (CAS no. 12008-41-2)
Relay output inductive load [A]2 A
Relay output ohmic load [A]3 A
Relay output voltage [V] AC230 V
SCIP dossier no.63ff497e-8c51-4844-9537-63d1cd363aac
Storage temperature [°C] [Max]70 °C
Storage temperature [°C] [Min]-40 °C
Supply voltage [V] AC230 V
Supply voltage [V] AC [max]244 V
Supply voltage [V] AC [min]207 V
Supply voltage frequency [Hz]50 Hz
Temperature sensors typePt 1000
Time switch power backup [h]10 h
Time switch typeWeek
User input typePush buttons

General specifications

Characteristic
Value
Gross weight0.433 Kilogram
Net weight0.377 Kilogram
Characteristic
Value
Volume0.854 Liter
Proposition 65Cancer and Reproductive Harm