Thermostatic injection valves, ammonia refrigerants-product-category

Thermostatic injection valves, ammonia refrigerants

Product types shown: 1

  • TEAT category image

    TEAT

    Refrigerant injection into the suction line

    TEAT valves are used to inject refrigerant into the suction line of the refrigeration system to reduce the high discharge temperatures that can occur when the system operates with highly superheated suction vapor.
    This applies when, for example:
    • A compressor runs either with low suction pressure or with high condensing temperature
    • A compressor runs with both low suction pressure and high condensing temperature. This applies especially to
      systems with R 22
    • A compressor receives highly superheated suction vapor
    • A compressor runs with capacity regulation by hot gas bypass

    Two-stage refrigeration plant

    TEAT valves are also used in two-stage refrigeration plant to control liquid injection into the intercooler. The bulb is installed on the discharge line from the high-pressure compressor. The theoretically obtainable discharge temperature for given operating conditions can be found in the h, log p diagram for the refrigerant concerned.

    Temperature regulation of the medium

    TEAT valves have a further application: the temperature regulation of the medium, e.g. the temperature of the oil in a screw compressor.