Danfoss logo
ETS 6

Electric expansion valve, ETS 6 - 18

034G5075

Connection type: Solder, ODF, Inlet size [mm]: 7.94, Outlet size [mm]: 7.94

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-30 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-22 °F
ApprovalCECQCEACLLC CDC TYSKRoHSUKCAUL
CE evaluatedYes
China RoHS complianceYes
Compatible Danfoss controllersEIM 336EKE 1AEKE 1BEKE 1C
Connection materialCopper
Connection typeSolder, ODF
DG Indicator ProfileNot relevant for dangerous goods
DirectionAngleway
EU RoHS complianceYes
EU RoHS exemption clauseNo
Flow directionBi-flow
Fluid Group2
Full travel time speed [s] [max]16.0 s
Full travel time speed [s] [min]6.0 s
Identical product034G5070
In scope of WEEE and contain batteriesNo
Inlet size [in]5/16 in
Inlet size [mm]7.94 mm
Lubricants compatibilityMOPOE
Manual operation optionAST-G service driverETS 6 Manual coil
Material DescriptionETS 6-18 Electric exp. valve
Max. Working Pressure [bar]47.0 bar
Max. Working Pressure [psig]681 psig
MaxOPD [bar]35.0 bar
MaxOPD [psig]507 psig
MOPD[bar/psi]35 bar
Motor typePermanent magnet stepper motor
Orifice size [mm]1.80 mm
Outlet size [in]5/16 in
Outlet size [mm]7.94 mm
Characteristic
Value
Packing formatMulti pack
Parts Program nameETS 6
PED categoryArt. 3, par. 3
Product accessoriesElectric valve accessories
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameElectric expansion valve
Product TypeETS 6 - 18
Quantity per packing format10 pc
Rated cap. conditions [IMP]Subcooling=32 ºFSuperheat=32 ºFtcond=100 ºFtevap=41 ºF
Rated cap. conditions [SI]Subcooling=0 ºCSuperheat=0 ºCtcond=38 ºCtevap=5 ºC
Rated cap. R404A/R507A [kW]7.30 kW
Rated cap. R404A/R507A [TR]2.07 TR
Rated capacity R134a [kW]8.10 kW
Rated capacity R134a [TR]2.30 TR
Rated capacity R22 [kW]10.30 kW
Rated capacity R22 [TR]2.93 TR
Rated capacity R407C [kW]10.60 kW
Rated capacity R407C [TR]3.01 TR
Rated capacity R410A [kW]12.10 kW
Rated capacity R410A [TR]3.44 TR
REACH Candidate List substancesNo
Refrigerant temperature [ºC] [max]70 °C
Refrigerant temperature [ºC] [min]-30 °C
Refrigerant temperature [ºF] [max]158 °F
Refrigerant temperature [ºF] [min]-22 °F
RefrigerantsR1234yfR134aR22/R407CR290R32R404A/R507AR407HR410AR448AR449AR449BR452AR452BR454AR454BR454CR455AR463AR513A
ServiceableNo
Step mode2-phase full stepHalf step (recommended)Microstep
Total steps480 (half steps)
UK RoHS complianceYes
UL approved refrigerantsR134aR22R404AR407CR410AR448AR449AR452AR507A
UL evaluatedYes

General specifications

Characteristic
Value
Gross weight0.077 Kilogram
Net weight0.05 Kilogram
Characteristic
Value
Volume0.487 Liter
EAN5702428909068