Danfoss logo
ETS 5M13, ETS 5M17, ETS 5M20, ETS 5M24  Elec. exp. valve L 14 x14 ODM_034G6204_034G6207

Electric expansion valve, ETS 5M24

034G6212

Connection type: Solder, ODM, Inlet size [mm]: 6.35, Outlet size [mm]: 6.35

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]60 °C
Ambient temperature range [°C] [min]-10 °C
Ambient temperature range [°F] [max]140 °F
Ambient temperature range [°F] [min]14 °F
China RoHS complianceYes
Compatible Danfoss controllersEIM 336EKE 1AEKE 1BEKE 1C
Connection materialCu-plated SS
Connection typeSolder, ODM
Design config. StyleL
DG Indicator ProfileNot relevant for dangerous goods
EU RoHS complianceOut of scope
Flow characteristicLinear
Flow directionBi-flow
In scope of WEEE and contain batteriesNo
Inlet size [in]1/4 in
Inlet size [mm]6.35 mm
Lubricants compatibilityPOE
Manual operation optionAST-G service driverManual coil
Material DescriptionETS 5M24 Elec. exp. valve L 14x14 ODM
Max. Working Pressure [bar]49.0 bar
Max. Working Pressure [psig]711 psig
MaxOPD [bar]35.0 bar
MaxOPD [psig]508 psig
MaxOPD reverse [bar]35 bar
MaxOPD reverse [psi]508.0 psi
Min. Leakage [cm³/min] @ 1 Mpa150 cm³/min
Motor typePermanent magnet stepper motor
Orifice size [mm]2.40 mm
Outlet size [in]1/4 in
Outlet size [mm]6.35 mm
Packing formatMulti pack
Parts Program nameETS 5M
PED categoryArt. 4, par. 3
Product accessoriesElectric valve accessories
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameElectric expansion valve
Product TypeETS 5M24
Quantity per packing format20 pc
Rated cap. conditions [SI]Subcooling=0 ºCSuperheat=0 ºCtcond=38 ºCtevap=5 ºC
Rated cap. R404A/R507A [kW]12.00 kW
Rated cap. R404A/R507A [TR]3.41 TR
Rated capacity R1234yf [kW]9.31 kW
Rated capacity R1234yf [TR]2.65 TR
Rated capacity R1234ze(E) [kW]9.58 kW
Rated capacity R1234ze(E) [TR]2.72 TR
Rated capacity R134a [kW]12.71 kW
Rated capacity R134a [TR]3.61 TR
Rated capacity R22 [kW]17.00 kW
Rated capacity R22 [TR]4.83 TR
Characteristic
Value
Rated capacity R290 [kW]17.64 kW
Rated capacity R290 [TR]5.02 TR
Rated capacity R32 [kW]29.88 kW
Rated capacity R32 [TR]8.50 TR
Rated capacity R407C [kW]17.71 kW
Rated capacity R407C [TR]5.04 TR
Rated capacity R407H [kW]19.79 kW
Rated capacity R407H [TR]5.63 TR
Rated capacity R410A [kW]20.23 kW
Rated capacity R410A [TR]5.75 TR
Rated capacity R448A [kW]17.00 kW
Rated capacity R448A [TR]4.83 TR
Rated capacity R449A [kW]16.62 kW
Rated capacity R449A [TR]4.73 TR
Rated capacity R449B [kW]16.90 kW
Rated capacity R449B [TR]4.81 TR
Rated capacity R452A [kW]12.81 kW
Rated capacity R452A [TR]3.64 TR
Rated capacity R452B [kW]23.20 kW
Rated capacity R452B [TR]6.60 TR
Rated capacity R454A [kW]17.25 kW
Rated capacity R454A [TR]4.90 TR
Rated capacity R454B [kW]23.45 kW
Rated capacity R454B [TR]6.67 TR
Rated capacity R454C [kW]14.77 kW
Rated capacity R454C [TR]4.20 TR
Rated capacity R455A [kW]16.30 kW
Rated capacity R455A [TR]4.63 TR
Rated capacity R513A [kW]10.79 kW
Rated capacity R513A [TR]3.07 TR
Rated capacity R515B [kW]9.28 kW
Rated capacity R515B [TR]2.64 TR
REACH Candidate List substancesNo
Refrigerant temperature [ºC] [max]70 °C
Refrigerant temperature [ºC] [min]-30 °C
Refrigerant temperature [ºF] [max]158 °F
Refrigerant temperature [ºF] [min]-22 °F
RefrigerantsR1234yfR1234ze(E)R134aR22R290R32R404A/R507AR407CR407HR410AR448AR449AR449BR452AR452BR454AR454BR454CR455AR463AR513AR515B
Relative humidity (RH) [%] [max]95 %
Relative humidity (RH) [%] [min]0 %
ServiceableNo
Step mode1-2 excitation (half step)2-2 excitation (full step)
Storage temperature range [°C] [max]70 °C
Storage temperature range [°C] [min]-30 °C
Storage temperature range [°F] [max]158 °F
Storage temperature range [°F] [min]-22 °F
Total steps480 (half steps)
UK RoHS complianceOut of scope
Valve open pulses@normal flow55 ± 16 steps
Valve open pulses@reverse flow15 ± 15 steps

General specifications

Characteristic
Value
Gross weight0.052 Kilogram
Net weight0.035 Kilogram
Volume0.251 Liter
Characteristic
Value
EAN5702428680547
Proposition 65Cancer and Reproductive Harm