Danfoss logo
ETS 400L - 500L

Electric expansion valve, ETS 500L

034G3664

Inlet connection type: Solder, ODF, Inlet size [in]: 2 5/8 in, Outlet size [in]: 3 1/8 in

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCECMIMCRNEACLLC CDC TYSKUAUKCAUL Recognized
Approval file nameMH7648
Balanced port [Yes/No]Yes
Body materialBrass
CE evaluatedYes
China RoHS complianceOut of scope
Compatible Danfoss controllersAK-XM 208CEKEEKFMXC
Connection materialCopper
Cv value [gal/min]31.330 gal/min
DG Indicator ProfileNot relevant for dangerous goods
DirectionStraightway
Electrical conn. Male/FemaleMale
Electrical connectionM12
Electrical connection size4 pin
Enclosure rating IPIP67
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Flow characteristicLinear
Flow directionBi-flow
Fluid Group2
Full travel time CurrDrive [s]16.7 s
Full travel time VoltDrive [s]33.3 s
In scope of WEEE and contain batteriesNo
Inlet connection typeSolder, ODF
Inlet size [in]2 5/8 in
Kv value [m³/h]27.100 m³/h
Lubricants compatibilityPOE
Manual operation optionAST-G service driver
Material DescriptionETS 500L Electric exp valve w. SG
Max allowed duty cycle [%]50 %
Max tot PowerCons CurrDrive[W]4.2 W
Max tot PowerCons VoltDrive[W]5.5 W
Max. Working Pressure [bar]37.0 bar
Max. Working Pressure [psig]536 psig
MaxOPD reverse [bar]10 bar
MaxOPD reverse [psi]145.0 psi
MaxOPD reverse CurrDrive [bar]10 bar
MaxOPD reverse CurrDrive [psi]145 psi
MaxOPD reverse VoltDrive [bar]10 bar
Characteristic
Value
MaxOPD reverse VoltDrive [psi]145 psi
Motor typeBi-polar
MWP [bar] CRN32 bar
MWP [psig] CRN463 psig
Operating current max. [A]0.40 A
Outlet connection typeSolder, ODF
Outlet size [in]3 1/8 in
Packing formatSingle pack
PED categoryI
Phase current (peak) [mA]283 mA
Phase current (RMS) [mA]200 mA
Phase inductance [µH]85000 μH
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameElectric expansion valve
Product TypeETS 500L
Quantity per packing format1 pc
Rated cap. cond. noteFull stroke open, normal flow
Rated cap. conditions [IMP]tcond=90 °Ftevap=40 °Ftliq=82 °F
Rated cap. conditions [SI]tcond=32 °Ctevap=5 °Ctliq=28 °C
Rated capacity R1234ze [kW]1396.00 kW
Rated capacity R1234ze [TR]402.00 TR
Rated capacity R134a [kW]1786.00 kW
Rated capacity R134a [TR]507.00 TR
Rated capacity R513A [kW]1535.00 kW
Rated capacity R513A [TR]442.00 TR
Rated capacity R515B [kW]1357.00 kW
Rated capacity R515B [TR]390.00 TR
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cobalt dichloride (CAS no. 7646-79-9)
Refrigerant temperature [ºC] [max]95 °C
Refrigerant temperature [ºC] [min]-40 °C
Refrigerant temperature [ºF] [max]203 °F
Refrigerant temperature [ºF] [min]-40 °F
RefrigerantsR1234ze(E)R134aR22R404AR407AR407CR407FR407HR410AR417AR422AR422BR422DR438AR442AR448AR449AR449BR450AR452AR463AR507AR513AR513BR515AR515B
SCIP dossier no.c81a3c50-9710-4373-be75-2652b16aea76
SCIP dossier product nameETS 175L-550L with sight glass
SightglassYes
Step mode2-phase full step
UK RoHS complianceYes with exemptions
UK RoHS exemption clause18
UL approved refrigerantsR1234ze(E)R134aR22R404AR407AR407CR407FR407HR410AR417AR422AR422BR422DR438AR442AR448AR449AR449BR450AR452AR463AR507AR513AR513BR515AR515B
UL evaluatedYes
Voltage [V] DC12.0 V

General specifications

Characteristic
Value
Gross weight4.795 Kilogram
Net weight3.88 Kilogram
Volume22.788 Liter
Characteristic
Value
EAN5715162497753
Proposition 65Cancer and Reproductive Harm