Danfoss logo
ETS 100

Electric expansion valve, ETS 50

034G1704

Inlet connection type: Solder ODF, Inlet size [in]: 1 1/8 in, Outlet size [in]: 1 3/8 in

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]60 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]140 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCEEACLLC CDC TYSKUKCAUL
Balanced port [Yes/No]Yes
CE evaluatedYes
China RoHS complianceYes
Compatible Danfoss controllersEKE 1AEKE 1BEKE 1C
Connection materialBi-metal: Steel/copper
DG Indicator ProfileNot relevant for dangerous goods
DirectionStraightway
Electrical conn. Male/FemaleMale
Electrical connectionM12
Electrical connection size4 pin
Enclosure rating IPIP67
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Flow directionBi-flow
Fluid Group2
Full travel time speed [s] [max]17.0 s
Full travel time speed [s] [min]8.5 s
In scope of WEEE and contain batteriesNo
Inlet connection typeSolder ODF
Inlet size [in]1 1/8 in
Lubricants compatibilityMOPOE
Manual operation optionAST-G service driver
Material DescriptionETS 50 Electric exp. valve w. SG
Max allowed duty cycle [%]100 %
Max tot PowerCons CurrDrive[W]1.3 W
Max tot PowerCons VoltDrive[W]5.5 W
Max. Working Pressure [bar]45.5 bar
Max. Working Pressure [psig]660 psig
MaxOPD [bar]33.0 bar
MaxOPD [psi]478.6 psi
MaxOPD reverse [bar]33 bar
MaxOPD reverse [psi]478.6 psi
Motor typeBi-polar
Outlet connection typeSolder ODF
Outlet size [in]1 3/8 in
Packing formatSingle pack
Characteristic
Value
PED categoryI
Phase current (peak) [mA]141 mA
Phase current (RMS) [mA]100 mA
Phase inductance [µH]85000 μH
Product accessoriesStepper valve accessories
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameElectric expansion valve
Product TypeETS 50
Quantity per packing format1 pc
Rated cap. cond. noteFull stroke open, normal flow
Rated cap. conditions [IMP]tcond=90 °Ftevap=40 °Ftliq=82 °F
Rated cap. conditions [SI]tcond=32 °Ctevap=5 °Ctliq=28 °C
Rated cap. R404A/R507A [kW]161.40 kW
Rated cap. R404A/R507A [TR]46.30 TR
Rated capacity R134a [kW]170.00 kW
Rated capacity R134a [TR]48.90 TR
Rated capacity R22 [kW]215.00 kW
Rated capacity R22 [TR]62.00 TR
Rated capacity R407C [kW]240.50 kW
Rated capacity R407C [TR]69.10 TR
Rated capacity R410A [kW]262.30 kW
Rated capacity R410A [TR]75.70 TR
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cobalt dichloride (CAS no. 7646-79-9)
Refrigerant temperature [ºC] [max]65 °C
Refrigerant temperature [ºC] [min]-40 °C
Refrigerant temperature [ºF] [max]150 °F
Refrigerant temperature [ºF] [min]-40 °F
RefrigerantsR1234ze(E)R134aR22R404AR407AR407CR407FR407HR410AR417AR422AR422BR422DR438AR442AR448AR449AR449BR450AR452AR463AR507AR513AR513BR515AR515B
Resistance [kOhm]0.1 kOhm
SCIP dossier no.c5625b77-53ec-4079-9d51-0ef83e9579dd
SCIP dossier product nameETS 50-100 with sight glass
ServiceableStepper valve spare parts
SightglassYes
Step mode2-phase full step
Total steps2625 (full steps)
UK RoHS complianceYes
UL approved refrigerantsR134aR22R404AR407AR407CR407FR410AR422BR422DR438AR448AR449AR450AR452AR507AR513A
UL evaluatedYes
Voltage [V] DC [max]13.8 V
Voltage [V] DC [min]11.5 V

General specifications

Characteristic
Value
Gross weight1.826 Kilogram
Net weight1.473 Kilogram
Volume6.248 Liter
Characteristic
Value
EAN5702428827034
Proposition 65Cancer and Reproductive Harm