Danfoss logo
ETS 100

Electric expansion valve, ETS 100

034G0505

Inlet connection type: Solder ODF, Inlet size [in]: 1 5/8 in, Outlet size [in]: 1 5/8 in

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]60 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]140 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCEEACLLC CDC TYSKUKCAUL
Balanced port [Yes/No]Yes
Basic Data Text TemplateETS 100 Electric Expansion Valve
CE evaluatedYes
China RoHS complianceOut of scope
Compatible Danfoss controllersEKE 1AEKE 1BEKE 1C
Connection materialBi-metal: Steel/copper
Contain batteriesNo
DG Indicator ProfileNot relevant for dangerous goods
DirectionStraightway
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Electrical conn. Male/FemaleMale
Electrical connectionM12
Electrical connection size4 pin
Enclosure rating IPIP67
Flow directionBi-flow
Fluid Group2
Full travel time speed [s] [max]23.0 s
Full travel time speed [s] [min]11.5 s
Inlet connection typeSolder ODF
Inlet size [in]1 5/8 in
Lubricants compatibilityMOPOE
Manual operation optionAST-G service driver
Material DescriptionETS 100 Electric exp valve
Max allowed duty cycle [%]100 %
Max tot PowerCons CurrDrive[W]1.3 W
Max tot PowerCons VoltDrive[W]5.5 W
Max. Working Pressure [bar]45.5 bar
Max. Working Pressure [psig]660 psig
MaxOPD [bar]33.0 bar
MaxOPD [psi]478.6 psi
MaxOPD reverse [bar]33 bar
MaxOPD reverse [psi]478.6 psi
Motor typeBi-polar
Outlet connection typeSolder ODF
Outlet size [in]1 5/8 in
Characteristic
Value
PED categoryI
Packing formatSingle pack
Phase current (RMS) [mA]100 mA
Phase current (peak) [mA]141 mA
Phase inductance [µH]85000 μH
Product TypeETS 100
Product accessoriesStepper valve accessories
Product groupExpansion valves
Product lineAir Conditioning and Commercial Refrigeration
Product nameElectric expansion valve
Quantity per packing format1 pc
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cobalt dichloride (CAS no. 7646-79-9)
Rated cap. R404A/R507A [TR]86.60 TR
Rated cap. R404A/R507A [kW]300.50 kW
Rated cap. cond. noteFull stroke open, normal flow
Rated cap. conditions [IMP]tcond=90 °Ftevap=40 °Ftliq=82 °F
Rated cap. conditions [SI]tcond=32 °Ctevap=5 °Ctliq=28 °C
Rated capacity R134a [TR]91.20 TR
Rated capacity R134a [kW]316.50 kW
Rated capacity R22 [TR]115.40 TR
Rated capacity R22 [kW]400.40 kW
Rated capacity R407C [TR]128.70 TR
Rated capacity R407C [kW]447.80 kW
Rated capacity R410A [TR]140.90 TR
Rated capacity R410A [kW]488.40 kW
Refrigerant temperature [ºC] [max]65 °C
Refrigerant temperature [ºC] [min]-40 °C
Refrigerant temperature [ºF] [max]150 °F
Refrigerant temperature [ºF] [min]-40 °F
RefrigerantsR1234ze(E)R134aR22R404AR407AR407CR407FR407HR410AR417AR422AR422BR422DR438AR442AR448AR449AR449BR450AR452AR463AR507AR513AR513BR515AR515B
Resistance [kOhm]0.1 kOhm
SCIP dossier no.c5625b77-53ec-4079-9d51-0ef83e9579dd
SCIP dossier product nameETS 50-100 with sight glass
ServiceableStepper valve spare parts
SightglassYes
Step mode2-phase full step
Total steps3530 (full steps)
UL approved refrigerantsR134aR22R404AR407AR407CR407FR410AR422BR422DR438AR448AR449AR450AR452AR507AR513A
UL evaluatedYes
Voltage [V] DC [max]13.8 V
Voltage [V] DC [min]11.5 V

General specifications

Characteristic
Value
Gross weight2.086 Kilogram
Net weight1.766 Kilogram
Volume6.248 Liter
Characteristic
Value
EAN/UPC5702428827300
Proposition 65Cancer and Reproductive Harm